DANH MỤC SẢN PHẨM
DỰ ÁN
Lượt Truy Cập
Previous
http://anphatautomation.com/MAG 6000 I/6000 I Ex d
MAG 6000 I/6000 I Ex d


Mã sản phẩm: 7ME6930
Tên sản phẩm: MAG 6000 I/6000 I Ex d




Mode of operation and design

 

Measuring principle

Electromagnetic with pulsed constant field

Empty pipe

Detection of empty pipe (special cable required in remote mounted installation)

Excitation frequency

Depend on sensor size

Electrode input impedance

> 1 x 1014 Ω

Input

 

Digital input

DC 11 ... 30 V, Ri = 4.4 kΩ

  • Activation time

50 ms

  • Current

IDC 11 V = 2.5 mA, IDC 30 V = 7 mA

Output

 

Current output

 
  • Signal range

0 ... 20 mA or 4 ... 20 mA (active/passive)

  • Load

< 800 Ω

  • Time constant

0.1 … 30 s, adjustable

Digital output

 
  • Frequency

0 … 10 kHz, 50 % duty cycle (uni-/bidirectional)

  • Time constant

0.1 … 30 s, adjustable

  • Pulse (passive)

DC 3 … 30 V, max 110 mA (30 mA Ex version), 200 Ω ≤ Ri ≤ 10 kΩ (powered from connected equipment)

  • Time constant

0.1 … 30 s, adjustable

Relay output

 
  • Time constant

Changeover relay, same as current output

  • Load

42 V AC/2 A, 24 V DC/1 A

Low flow cut off

0 … 9.9 % of maximum flow

Galvanic isolation

All inputs and outputs are galvanic isolated

Max. measuring error

 
  • MAG 6000 I/MAG 6000 I Ex d

0.25 % of rate

Rated operation conditions

 

Ambient temperature

 
  • Operation
 
  • MAG 6000 I

-20 … +60 °C (-4 … +140 °F)

  • MAG 6000 I Ex

-10 … +60 °C (+14 … +140 °F)

  • Storage

-40 … +70 °C (-40 … +158 °F)

Mechanical load

18 ... 1000 Hz random in x, y z, directions for 2 hours according to EN 60068-2-36

Transmitter: 1.14 grms

Degree of protection

IP67/NEMA 4X to IEC 529 and DIN 40050 (1 mH2O 30 min.)

EMC performance

EN 61326

Display and keypad

 

Totalizer

Two eight-digit counters for forward, net or reverse flow

Display

Background illumination with alphanumeric text, 3 x 20 characters to indicate flow rate, totalized values, settings and faults; Reverse flow indicated by negative sign

Keypad

Capacitive touch keypad with LED light for feedback indication

Time constant

Time constant as current output time constant

Design

 

Enclosure material

Die cast aluminium, painted

  • Wall mounting

Wall mounting bracket enclosed for remote version

Dimensional drawings

See dimensional drawings

Weight

See dimensional drawings

Power supply

  • Non Ex d: 18 ... 90 V DC; 
    115 ... 230 V AC; 50 ... 60 Hz
  • Ex d: 18 ... 30 V DC
  • Ex d: 115 ... 230 V AC; 
    50 ... 60 Hz

Power consumption

  • 230 V AC: 21.5 VA
  • 24 V DC: 12 W, IN = 380 mA, IST = 1 A (3 ms)

Certificates and approvals

 

MAG 6000 I

  • CE
  • C-tick
  • FM Class 1, div 2
  • FM Class 1, Zone 2
  • CSA Class 1, div 2
  • CSA Class 1, Zone 2

MAG 6000 I Ex (to be used with ATEX 2G D sensors)

  • SIRA 03 ATEX 2072X
  • EX II 2 (1) (2) G D
  • EEx d e [ia] ia [ib] ib IIC, T6

Cable entries

Remote installation

  • MAG 6000 I

2 x M25 (for supply/output) and 2 x M16 (for sensor connection) or 2 x ½ NPT (for supply/output) and 2 x M16 ( for sensor connection)

  • MAG 6000 I Ex ATEX 2G D

2 x M20 (for supply/output) and 2 x M16 (for sensor connection)

Communication

 
  • Non ATEX versions

HART, MODBUS RTU/RS 485, FOUNDATION Fieldbus H1, DeviceNet, PROFIBUS PA, PROFIBUS DP add-on modules

  • ATEX 2G D

HART, PROFIBUS PA, FOUNDATION Fieldbus H1 available as integrated version

 


Overview:

 

Features:

 

Video clips:

 

Screen shots:

 

Links:

 







Hỗ Trợ Trực Tuyến
Hỗ Trợ Kỹ Thuật
090 680 83 10