| HART | PROFIBUS PA or Foundation fieldbus |
Input | |
Measured variable | Gage pressure |
Spans (infinitely adjustable) or nominal measuring range and max. permissible test pressure | Span | Max. perm. test pressure | Nominal measuring range | Max. perm. test pressure |
| 0.01 ... 1 bar g (0.15 ... 14.5 psi g) | 6 bar g (87 psi g) | 1 bar g (14.5 psi g) | 6 bar g (87 psi g) |
| 0.04 ... 4 bar g (0.58 ... 58 psi g) | 10 bar g (145 psi g) | 4 bar g (58 psi g) | 10 bar g (145 psi g) |
| 0.16 ... 16 bar g (2.32 ... 232 psi g) | 32 bar g (464 psi g) | 16 bar g (232 psi g) | 32 bar g (464 psi g) |
Lower measuring limit | | |
Measuring cell with silicone oil filling | 100 mbar a (1.45 psi a) |
Upper measuring limit | 100 % of max. span |
Output | | |
Output signal | 4 ... 20 mA | Digital PROFIBUS PA or Foundation fieldbus signal |
Lower limit (infinitely adjustable) | 3.55 mA, factory preset to 3.84 mA | - |
Upper limit (infinitely adjustable) | 23 mA, factory preset to 20.5 mA or optionally set to 22.0 mA | - |
Load | |
Without HART communication | RB ≤ (UH - 10.5 V)/0.023 A in Ω, UH : Power supply in V | - |
With HART communication | RB = 230 ... 500 Ω (SIMATIC PDM) or RB = 230 ... 1100 Ω (HART Communicator) | - |
Physical bus | - | IEC 61158-2 |
With polarity reversal protection | - | Yes |
Accuracy | Acc. to EN 60770-1 |
Reference conditions (All error data refer always refer to the set span) | Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, silicone oil filling, room temperature 25 °C (77 °F)) r: Span ratio (r = max. span / set span) |
Error in measurement and fixed-point setting (including hysteresis and repeatability) | |
Linear characteristic | | ≤ 0.075 % |
r ≤ 10 | ≤ (0.0029 · r + 0.071)% | |
10 < r ≤ 30 | ≤ (0.0045 · r + 0.071)% | |
30 < r ≤ 100 | ≤ (0.005 · r + 0.05)% | |
Long-term drift (temperature change ±30 °C (±54 °F)) | ≤ (0.25 · r)% every 5 years | ≤ 0.25 % every 5 years |
Influence of ambient temperature | |
at -10 ... +60 °C (14 ... 140 °F) | ≤ (0.08 · r + 0.1)% | ≤ 0.3 % |
at -40 ... -10 °C and +60 ... +85 °C (-40 ... +14 °F and 140 ... 185 °F) | ≤ (0.1·r + 0.15) %/10 K | ≤ 0.25 %/10 K |
Influence of the medium temperature (only with flush-mounted diaphragm) | |
Temperature difference between medium temperature and ambient temperature | 3 mbar/10 K (0.04 psi/10 K) |
Influence of mounting position | ≤ 0.1 mbar g (0.00145 psi g) per 10° inclination |
Measured Value Resolution | - | 3 · 10-5 of nominal measuring range |
Rated operating conditions | |
Degree of protection (to EN 60529) | IP65, IP68, NEMA 4X, enclosure cleaning, resistant to lyes, steam to 150° C (302 °F) |
Temperature of medium | -20 ... +100 °C (-4 ... +212 °F) |
Ambient conditions | |
Ambient temperature | -20 ... +85 °C (-4 ... +185 °F) |
Storage temperature | -50 ... +85 °C (-58 ... +185 °F) |
Climatic class | |
Condensation | Permissible |
Electromagnetic Compatibility | |
Emitted interference | Acc. to EN 50081-1 |
Interference immunity | Acc. to EN 61326 and NAMUR NE 21 |
Design | |
Weight (without options) | ≈ 1.5 kg (≈ 3.3 lb) |
Enclosure material | Low-copper die-cast aluminum GD-AlSi 12 |
Wetted parts materials | |
Gasket (standard) | PTFE flat gasket |
O-ring (minibolt) | FPM (Viton) or optionally: FFPM or NBR |
Measuring cell filling | Silicone oil or inert filling liquid |
Process connection (standard) | Flush-mounted, 1½", PMC Standard design |
Process connection (minibolt) | Flush-mounted, 1", minibolt design |
Power supply UH | | Supplied through bus |
Terminal voltage on transmitter | 10.5 ... 45 V DC 10.5 ... 30 V DC in intrinsically-safe mode | - |
Separate 24 V power supply necessary | - | No |
Bus voltage | |
Not Ex | - | 9 ...32 V |
With intrinsically-safe operation | - | 9 ...24 V |
Current consumption | |
Basic current (max.) | - | 12.5 mA |
Startup current ≤ basic current | - | Yes |
Max. current in event of fault | - | 15.5 mA |
Fault disconnection electronics (FDE) available | - | Yes |
Certificates and approvals | | |
Classification according to PED 97/23/EC | For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) |