DANH MỤC SẢN PHẨM
DỰ ÁN
Lượt Truy Cập
Previous
http://anphatautomation.com/SITRANS P Compact, for pressure and absolute pressure
SITRANS P Compact, for pressure and absolute pressure


Mã sản phẩm: 7MF8010
Tên sản phẩm: SITRANS P Compact, for pressure and absolute pressure




Pressure transmitters for food, pharmaceuticals and biotechnology

Mode of operation

 

Measuring principle

Piezo-resistive

Input

 

Measured variable

Gage or absolute pressure

Measuring range

0 ... 160 mbar (0 ... 2.32 psi)
... 
0 ... 40 bar (0 ... 580 psi)

Output

 

Output signal

 
  • Two-wire system

4 ... 20 mA

  • 3-wire system

0 ... 20 mA

Measuring accuracy

to EN 60770-1

Linearity error including hysteresis (reference point adjustment)

= 0.2 % of full-scale value

Adjustment accuracy

= ± 0.2 % of full-scale value

Response time

< 20 ms

Influence of ambient temperature

 

On the enclosure

 
  • Zero

< 0.2 %/10 K of full-scale value

  • Measured span

< 0.2 %/10 K of full-scale value

On the process connection (remote seals)

Zero error (depends on design)

  • Flange remote seal
 
  • DN 25 / 1"

4.8 mbar/10 K (0.070 psi/10 K)

  • DN 32 / 1¼"

2.3 mbar/10 K (0.033 psi/10 K)

  • DN 40 / 1½"

1.6 mbar/10 K (0.023 psi/10 K)

  • DN 50 / 2"

0.6 mbar/10 K (0.009 psi/10 K)

  • Clamp-on seal
 
  • DN 25 / 1"

9.5 mbar/10 K (0.138 psi/10 K)

  • DN 32 / 1¼"

4.1 mbar/10 K (0.060 psi/10 K)

  • DN 40 / 1½"

3.9 mbar/10 K (0.057 psi/10 K)

  • DN 50 / 2"

3.9 mbar/10 K (0.057 psi/10 K)

The zero error specified for the process connection should be considered as a guideline for a standard design. We will produce a detailed system calculation on request. Systems with reduced remote seal errors are available on request.

Rated conditions

 

Installation conditions

 
  • Mounting position

Any, vertical as standard

Ambient conditions

 
  • Ambient temperature

-10 ... +70 °C (14 ... 158 °F)

  • Storage temperature

-10 ... +90 °C (14 ... 194 °F)

  • Process temperature

Max. 200 °C (392 °F), depending on design

  • Degree of protection (to EN 60529)

IP65, optional IP67

  • Electromagnetic compatibility
 
  • Emitted interference

To EN 50081 Part 1, issue 1993 (residential and industrial areas). The unit has no own emissions.

  • Noise immunity to

EN 50082 Part 2, issue March 1995 (industrial areas)

Construction

 

Weight (without remote seal)

 
  • Field housing

˜ 460 g (˜ 1.01 lb)

  • Enclosure with plug

˜ 200 g (˜ 0.44 lb)

Enclosure

 
  • Designs
  • Field housing IP65 or IP67, with screwed gland
  • Angled plug DIN 43650, IP65
  • Cable connection, IP67
  • Round plug connector M12, IP65
  • Material

Stainless steel, mat. No. 1.4404/316L/1.4305

Material of union nut

Polyamide (with electrical connection using plug or cable)

Electronics unit potted with silicone

Internal ventilation for measuring ranges < 16 bar (< 232 psi), through housing thread or connecting cable depending on design

Process connection

 
  • Versions

See ordering data

  • Material of coupling

Stainless steel, mat. No. 1.4404/316L

Power supply

 

Terminal voltage on transmitter

10 ... 30 V DC

Rated voltage

24 V DC

Certificates and approvals

 

Classification according to pressure equipment directive (DRGL 97/23/EC)

For gases of fluid group 1 and liquids of fluid group 1; complies with the requirements of Article 3, paragraph 1 (appendix 1); assigned to category III, conformity evaluation module H by the TÜV Nord

Explosion protection

 
  • Intrinsic safety "i"

TÜV 03 ATEX 2099 X

  • Identification

Ex II 2G EEx ib IIC T6

 


Overview:

 

Features:

 

Video clips:

 

Screen shots:

 

Links:

 







Hỗ Trợ Trực Tuyến
Hỗ Trợ Kỹ Thuật
090 680 83 10