| HART | PROFIBUS PA |
input | |
Measured variable | Gage pressure (flush-mounted) |
Spans (infinitely adjustable) or nominal measuring range and max. pemissible test pressure | Measured span | Max. perm. test pressure | Nominal measuring range | Max. perm. test pressure |
| 0.01 ... 1 bar g (0.15 ... 14.5 psi g) | 6 bar g (87 psi g) | 1 bar g (14.5 psi g) | 6 bar g (87 psi g) |
| 0.04 ... 4 bar g (0.58 ... 58 psi g) | 10 bar g (145 psi g) | 4 bar g (58 psi g) | 10 bar g (145 psi g) |
| 0.16 ... 16 bar g (2.3 ... 232 psi g) | 32 bar g (464 psi g) | 16 bar g (232 psi g) | 32 bar g (464 psi g) |
| Depending on the process connection, the span may differ from these values | Depending on the process connection, the nominal measuring range may differ from these values |
Lower measuring limit | |
- Measuring cell with silicone oil
| 100 mbar a (1.45 psi a) |
Upper measuring limit | |
- Measuring cell with silicone oil
| 100 % of max. span | 100 % of the max. nominal measuring range |
Output | |
Output signal | 4 ... 20 mA | Digital PROFIBUS PA signal |
Physical bus | - | IEC 61158-2 |
With polarity reversal protection | No | Yes |
Electrical damping T63(step width 0.1 s) | Set to 0.1 s (0 ... 100 s) |
Measuring accuracy | to EN 60770-1 |
Reference conditions | Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, measuring cell with silicone oil, room temperature 25 °C (77 °F), span ratio (r = max. span / set span) |
Measurement deviation with cut-off point setting, including hysteresis and repeatability. | |
Linear characteristic curve | | ≤ 0.075 % |
| ≤ (0.0029 · r + 0.071)% | |
| ≤ (0.0045 · r + 0.071)% | |
| ≤ (0.005 · r + 0.05)% | |
Settling time T63 without electrical damping | Approx. 0.2 s |
Long-term drift at ±30 °C (±54 °F) | ≤ (0.25 · r)%/5 years | ≤ 0.25 %/5 years |
Influence of ambient temperature | |
- at -10 ... +60 °C (14 ... 140 °F)
| ≤ (0.1 · r + 0.2)% | ≤ 0.3 % |
- at -40 ... -10 °C and +60 ... +85 °C
(-40 ... 14 °F and 140 ... 185 °F)
| ≤ (0.1·r + 0.15) %/10 K | ≤ 0.25 %/10 K |
Influence of the medium temperature (only with front-flush diaphragm) | |
- Temperature difference between medium temperature and ambient temperature
| 3mbar/10 K (0.04 psi/10 K) |
Rated conditions | |
Installation conditions | |
Ambient temperature | Observe the temperature class in areas subject to explosion hazard. |
- Measuring cell with silicone oil
| -40 ... +85 °C (-40 ... +185 °F) |
| -30 ... +85 °C (-22 ... +185 °F) |
| -50 ... +85 °C (-58 ... +185 °F) |
Climatic category | |
Condensation | Permissible |
Degree of protection to EN 60529 | IP65, IP68, NEMA X, enclosure cleaning, resistant to lyes, steam to 150° C (302 °F) |
Electromagnetic compatibility | |
- Emitted interference and noise immunity
| To EN 61326 and NAMUR NE 21 |
Medium conditions | |
Temperature of medium | |
- Measuring cell with silicone oil
| -40 ... +100 °C (-40 ... +212 °F) |
Construction | |
Weight (without options) | Approx. 1 kg (2.2 lb) |
Enclosure material | Stainless steel, mat. No. 1.4301/304 |
Material of parts in contact with the medium | |
| Hastelloy C276, mat. No. 2.4819 |
| Silicone oil |
Power supply UH | |
Terminal voltage on transmitter | 10.5 ... 42 V DC for intrinsically-safe operation: 10.5 ... 30 V DC | Supplied through bus |
Separate power supply | - | Not necessary |
Bus voltage | | |
| - | 9 ... 32 V |
- For intrinsically-safe operation
| - | 9 ... 24 V |
Current consumption | | |
| - | 12.5 mA |
- Startup current ≤ basic current
| - | Yes |
- Max. fault current in the event of a fault
| - | 15.5 mA |
Fault disconnection electronics (FDE) | - | Available |
Certificates and approvals | |
Classification according to pressure equipment directive (DRGL 97/23/EC) | For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of Article 3, paragraph 3 (sound engineering practice) |
Explosion protection | |
Intrinsic safety "i" | PTB 05 ATEX 2048 |
Identification | Ex II 1/2 G EEx ia/ib IIB/IIC T4, T5, T6 |
Permissible ambient temp. | |
| -40 ... +85 °C (-40 ... +185 °F) |
| -40 ... +70 °C (-40 ... +158 °F) |
| -40 ... +60 °C (-40 ... +140 °F) |
Interface | To certified intrinsically-safe circuits with maximum values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 Ω | To certified intrinsically-safe circuits with maximum values: FISCO supply unit: Ui = 17.5 V, Ii = 380 mA, Pi = 5.32 W Linear barrier: Ui = 24 V, Ii = 250 mA, Pi = 1.2 W |
Effective inner capacitance: | Ci = 6 nF | Ci = 1.1 nF |
Effective inner inductance: | Li = 0.4 mH | Li ≤ 7 μH |
Explosion protection to FM for USA and Canada (cFMUS) | | |
- Identification (DIP) or (IS); (NI)
| Certificate of Compliance 3025099 CL I, DIV 1, GP ABCD T4 ... T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4 ... T6; CL I, DIV 2, GP ABCD T4 ... T6; CL II, DIV 2, GP FG; CL III |
- Identification (DIP) or (IS)
| Certificate of Compliance 3025099C CL I, DIV 1, GP ABCD T4 ... T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC 4 ... T6; CL I, DIV 2, GP ABCD T4 ... T6; CL II, DIV 2, GP FG; CL III |