Input | |
Resistance thermometer | |
Measured variable | Temperature |
Sensor type | |
| Pt25 … Pt1000 |
- To JIS C 1604; a=0.00392 K-1
| Pt25 … Pt1000 |
| Ni25 … Ni1000 |
| over special characteristic (max. 30 points) |
Sensor factor | 0.25 ... 10 (adaptation of the basic type, e.g. Pt100 to version Pt25 ... Pt1000) |
Units | °C or °F |
Connection | |
| 1 resistance thermometer (RTD) in 2-wire, 3-wire or 4-wire system |
- Generation of average value
| 2 identical resistance thermometers in 2-wire system for generation of average temperature |
| 2 identical resistance thermometers (RTD) in 2-wire system (RTD 1 – RTD 2 or RTD 2 – RTD 1) |
Interface | |
| Parameterizable line resistance ≤ 100 Ω (loop resistance) |
| No balancing required |
| No balancing required |
Sensor current | ≤ 0.45 mA |
Response time T63 | ≤ 250 ms for 1 sensor with open-circuit monitoring |
Open-circuit monitoring | Always active (cannot be disabled) |
Short-circuit monitoring | can be switched off (value is adjustable) |
Measuring range | Parameterizable (see table "Digital measuring errors") |
Min. measured span | 10 °C (18 °F) |
Characteristic curve | Temperature-linear or special characteristic |
Resistance-based sensors | |
Measured variable | Actual resistance |
Sensor type | Resistance-based, potentiometers |
Units | Ω |
Connection | |
| 1 resistance-based sensor (R) in 2-wire, 3-wire or 4-wire system |
- Generation of average value
| 2 resistance-based sensors in 2-wire system for generation of average value |
| 2 resistance thermometers in 2-wire system (R1 – R2 or R2 – R1) |
Interface | |
| Parameterizable line resistance ≤ 100 Ω (loop resistance) |
| No balancing required |
| No balancing required |
Sensor current | ≤ 0.45 mA |
Response time T63 | ≤ 250 ms for 1 sensor with open-circuit monitoring |
Open-circuit monitoring | Always active (cannot be disabled) |
Short-circuit monitoring | can be switched off (value is adjustable) |
Measuring range | Parameterizable, max. 0 ... 2200 Ω (see Table "Digital measuring errors") |
Min. measured span | 5 Ω ... 25 Ω (see Table "Digital measuring errors") |
Characteristic curve | Resistance-linear or special characteristic |
Thermocouples | |
Measured variable | Temperature |
Sensor type (thermocouples) | |
| Pt30Rh-Pt6Rh to DIN IEC 584 |
| W5 %-Re acc. to ASTM 988 |
| W3 %-Re acc. to ASTM 988 |
| NiCr-CuNi to DIN IEC 584 |
| Fe-CuNi to DIN IEC 584 |
| NiCr-Ni to DIN IEC 584 |
| Fe-CuNi to DIN 43710 |
| NiCrSi-NiSi to DIN IEC 584 |
| Pt13Rh-Pt to DIN IEC 584 |
| Pt10Rh-Pt to DIN IEC 584 |
| Cu-CuNi to DIN IEC 584 |
| Cu-CuNi to DIN 43710 |
Units | °C or °F |
Connection | |
| 1 thermocouple (TC) |
- Generation of average value
| 2 identical thermocouples (TC) |
| 2 identical thermocouples (TC) TC1 – TC2 or TC2 – TC1 |
Response time T63 | ≤ 250 ms for 1 sensor with open-circuit monitoring |
Open-circuit monitoring | can be switched off |
Cold junction compensation | |
| With integrated Pt100 resistance thermometer |
| With external Pt100 IEC 60571 (2-wire or 3-wire connection) |
| Cold junction temperature can be set as fixed value |
Measuring range | Parameterizable (see table "Digital measuring errors") |
Min. measured span | Min. 50 ... 100 °C (90 ... 180 °F) (see table "Digital measuring errors") |
Characteristic curve | Temperature-linear or special characteristic |
mV sensor | |
Measured variable | DC voltage |
Sensor type | DC voltage source (DC voltage source possible over an externally connected resistor) |
Units | mV |
Response time T63 | ≤ 250 ms for 1 sensor with open-circuit monitoring |
Open-circuit monitoring | can be switched off |
Measuring range | Parameterizable max. -100 … 1100 mV |