Input

 

Analog-to-digital conversion

 
  • Measurement rate

< 50 ms

  • Resolution

24-bit

Resistance thermometer

 

Pt25 ... Pt1000 to IEC 60751/JIS C 1604

 
  • Measuring range

-200 ... +850 °C (-328 ... +1562 °F)

Ni25 ... Ni1000 to DIN 43760

 
  • Measuring range

-60 ... +250 °C (-76 ... +482 °F)

Cu10 ... Cu1000, α = 0.00427

 
  • Measuring range

-50 ... +200 °C (-58 ... +392 °F)

Line resistance per sensor cable

Max. 50 Ω

Sensor current

Nominal 0.2 mA

Sensor fault detection

 
  • Sensor break detection

Yes

  • Sensor short-circuit detection

Yes, < 15 Ω

Resistance-based sensors

 

Measuring range

0 Ω ... 10 kΩ

Line resistance per sensor cable

Max. 50 Ω

Sensor current

Nominal 0.2 mA

Sensor fault detection

 
  • Sensor break detection

Yes

  • Sensor short-circuit detection

Yes, < 15 Ω

Thermocouple

 

to IEC 584

Measuring range

  • Type B

400 ... 1820 °C (752 ... 3308 °F)

  • Type E

-100 ... +1000 °C (-148 ... +1832 °F)

  • Type J

-100 ... +1000 °C (-148 ... +1832 °F)

  • Type K

-100 ... +1200 °C (-148 ... +2192 °F)

  • Type N

-180 ... +1300 °C (-292 ... +2372 °F)

  • Type R

-50 ... +1760 °C (-58 ... +3200 °F)

  • Type S

-50 ... +1760 °C (-58 ... +3200 °F)

  • Type T

-200 ... +400 °C (-328 ... +752 °F)

to DIN 43710

 
  • Type L

-200 ... +900 °C (-328 ... +1652 °F)

  • Type U

-200 ... +600 °C (-328 ... +1112 °F)

to ASTM E988-90

 
  • Type W3

0 ... 2300 °C (32 ... +4172 °F)

  • Type W5

0 ... 2300 °C (32 ... +4172 °F)

External cold junction compensation

-40 ... +135 °C (-40 ... +275 °F)

Sensor fault detection

 
  • Sensor break detection

Yes

  • Sensor short-circuit detection

Yes, < 3 mV

  • Sensor current in the event of open-circuit monitoring

4 μA

mV sensor - voltage input

 

Measuring range

-800 ... +800 mV

Input resistance

10 MΩ

Output

 

Filter time (programmable)

0 ... 60 s

Update time

< 400 ms


Measuring accuracy

  

Accuracy is defined as the higher value of general values and basic values.

General values

  

Type of input

Absolute accuracy

Temperature coefficient

All

≤ ±0.05 % of measured value

≤ ±0.002 % of measured value / °C

Basic values

  

Type of input

Basic accuracy

Temperature coefficient

Pt100 and Pt1000

≤± 0.1 °C

≤± 0.002 °C / °C

Ni100

≤± 0.15 °C

≤± 0.002 °C / °C

Cu10

≤± 1.3 °C

≤± 0.02 °C / °C

Resistance-based sensors

≤± 0.05 °Ω

≤± 0.002 °Ω / °C

Voltage source

≤± 10 μV

≤± 0.2 % μV / °C

Thermocouple, type:
E, J, K, L, N, T, U

≤± 0.5 °C

≤± 0.01 °Ω / °C

Thermocouple, type:
B, R, S, W3, W5

≤± 1 °C

≤± 0.025 % °C / °C

Cold junction compensation

≤± 0.5 °C

 

Reference conditions

  

Warming-up time

30 s

 

Signal-to-noise ratio

Min. 60 dB

 

Calibration condition

20 ... 28 °C (68 ... 82 °F)

 

Conditions of use

 

Ambient conditions

 

Permissible ambient temperature

-40 ... +85 °C (-40 ... +185 °F)

Permissible storage temperature

-40 ... +85 °C (-40 ... +185 °F)

Relative humidity

≤ 98 %, with condensation

Electrically isolated

 
  • Without Ex

Input against output 1 kVeff

  • With Ex

Input against output 500 Veff

Mechanical testing

 
  • Vibrations (DIN class B) to

IEC 60068-2-6 and IEC 60068-2-64
4 g/2 ... 100 Hz

Electromagnetic compatibility

 

EMC noise voltage influence

< ±0.1 % of span

Extended EMC noise immunity:
NAMUR NE 21, criterion A, Burst

< ±1 % of span

EMC 2004/108/EC Emission and Noise Immunity to

EN 61326

Construction

 

Material

Molded plastic

Weight

55 g (0.12 lb)

Dimensions

See Dimensional drawings

Cross-section of cables

Max. 2.5 mm2 (AWG 13)

Degree of protection

 
  • Transmitter enclosure

IP40

  • Terminal

IP00

Auxiliary power supply

 

Power supply

 
  • Standard, Ex "nA", Ex "nL", NI

9.0 ... 32 V DC

  • ATEX, FM, UL and CSA

9.0 ... 30 V DC

  • In FISCO/FNICO installations

9.0 ... 17.5 V DC

Power consumption

< 11 mA

Max. increase in power consumption in the event of a fault

< 7 mA


Certificates and approvals

 

Explosion protection ATEX

 

EC type test certificate

KEMA 06 ATEX 0264 X

  • "Intrinsic safety" type of protection

II 1 GD EEx ia IIC T4 ... T6
T65 °C ... T105 °C

II 2(1) GD EEx ib [ia] IIC T4 ... T6
T65 °C ... T105 °C

EC type test certificate

KEMA 06 ATEX 0263 X

  • Type of protection for "equipment is non-arcing"

II 3 G EEx nA [nL] IIC T4 ... T6
II 3 G EEx nL IIC T4 ... T6

Explosion protection: FM for USA

 
  • FM approval

FM 3027985

  • Degree of protection
  • IS/Cl I/Div 1/Groups ABCD T4, T5, T6, FISCO
  • IS/Cl I/ZN 0/AEx ia, IIC T4, T5, T6, FISCO
  • NI/Cl I/Div 2/Groups ABCD T4, T5, T6, FNICO

Explosion protection CSA for Canada

 
  • CSA approval

CSA 1861385

  • Degree of protection
  • IS/Cl I/Div 1/Groups ABCD T4, T5, T6
  • Ex ia IIC T4/T5/T6
    Ex ib [ia] IIC T4/T5/T6
  • Cl I/Div 2/Groups ABCD, T4, T5, T6
  • Ex nA IIC T4/T5/T6
    Cl I/ZN 2/AEx nA II T4, T5, T6

Communication

 

Parameterization interface

 
  • PROFIBUS PA connection
 
  • Protocol

Profile 3.0

  • Address (for delivery)

126

  • FOUNDATION fieldbus connection
 
  • Protocol

FF protocol

  • Functionality

Basic or LAS

  • Version

ITK 4.6

  • Function blocks

2 x analog and 1 x PID

Factory setting

only for SITRANS TH400 PA

 

Sensor

Pt100 (IEC)

Type of connection

3-wire circuit

Unit

°C

Failure mode

Last valid value

Filter time

0 s

PA address

126

PROFIBUS Ident No.

Manufacturer-specific

only for SITRANS TH400 FF

 

Sensor

Pt100 (IEC)

Type of connection

3-wire circuit

Unit

°C

Failure mode

Last valid value

Filter time

0 s

Node address

22

 