Input | |
Selectable filters to suppress the line frequency | 50 Hz, 60 Hz, also 10 Hz for special applications (line frequency filter is similar with measuring frequency) |
Resistance thermometer | |
Measured variable | Temperature |
Measured range | Parameterizable |
Measured span | Min. 25 °C (45 °F) x 1/scaling factor |
Sensor type | |
| Pt100 (DIN IEC 751) |
| Pt100 (JIS C1604-81) |
| Ni100 (DIN 43760) |
- Special type (RRTD ≤ 500 Ω)
| Multiples or parts of the defined characteristic values can be parameterized (e.g. Pt500, Ni120) |
Voltage measurement | Temperature-linear, resistance-linear or customer-specific |
Type of connection | - Normal connection
- Sum or parallel connection
- Mean-value or differential connection
|
Connection | 2, 3 or 4-wire circuit |
Measuring range limits | Depending on type of connected thermometer (defined range of resistance thermometer) |
Sensor breakage monitoring | Monitoring of all connections for open-circuit (function can be switched off) |
Sensor short-circuit monitoring | Parameterizable response threshold (function can be switched off) |
Resistance-based sensors, potentiometers | |
Measured variable | Ohmic impedance |
Measured range | Parameterizable |
Measured span | Min. 10 Ω |
Voltage measurement | Resistance-linear or customer-specific |
Type of connection | - Normal connection
- Differential connection
- Mean-value connection
|
Connection | 2, 3 or 4-wire circuit |
Input range | 0 ... 6000 Ω; with mean-value and difference circuits: 0 ... 3000 Ω |
Sensor breakage monitoring | Monitoring of all connections for open-circuit (function can be switched off) |
Sensor short-circuit monitoring | Parameterizable response threshold (function can be switched off) |
Thermocouple elements | |
Measured variable | Temperature |
Measured range | Parameterizable |
Measured span | Min. 50 °C (32.22 °C) x 1/scaling factor |
Measuring range limits | Depend. on type of thermocouple element |
Thermocouple | Type B: Pt30 %Rh/Pt6 %Rh (DIN IEC 584) |
| Type C W5 %-Re (ASTM 988) |
| Type D W3 %-Re (ASTM 988) |
| Type E: NiCr/CuNi (DIN IEC 584) |
| Type J: Fe/CuNi (DIN IEC 584) |
| Type K: NiCr/Ni (DIN IEC 584) |
| Type L Fe-CuNi (DIN 43710) |
| Type N: NiCrSi-NiSi (DIN IEC 584) |
| Type R: Pt13 %Rh/Pt (DIN IEC 584) |
| Type S: Pt10 %Rh/Pt (DIN IEC 584) |
| Type T: Cu/CuNi (DIN IEC 584) |
| Type U: Cu/CuNi (DIN 43710) |
| Special type (-10 mV ≤ UTC ≤ 100 mV) |
Voltage measurement | Temperature-linear, voltage-linear or customer-specific |
Type of connection | - Normal connection
- Sum connection
- Mean-value connection
- Differential connection
|
Cold junction compensation | None, internal measurement, external measurement or predefined fixed value |
Sensor breakage monitoring | Function can be switched off |
mV sensors | |
Measured variable | DC voltage |
Measured range | Parameterizable |
Measured span | Min. 4 mV |
Input range | -120 ... +1000mV |
Voltage measurement | Voltage-linear or customer-specific |
Overload capacity of inputs | Max. ± 3.5 V |
Input resistance | ≥ 1 Ω |
Sensor current | Approx. 180 μA |
Sensor breakage monitoring | Function can be switched off |
V sources | |
Measured variable | DC voltage |
Measured range | Parameterizable |
Voltage measurement | Voltage-linear or customer-specific |
Input range/min. span | |
- Devices with 7NG3242-xxxx1or 7NG3242-xxxx 0 with U/I plug
| -1.2 V ... +10 V 0.04 V |
- Devices with 7NG3242-xxxx2
| -12 V ... +100 V 0.4 V |
- Devices with 7NG3242-xxxx3
| -120 V ... +140 V 4.0 V |
Sensor breakage monitoring | Not possible |
μA, mA sources | |
Measured variable | DC voltage |
Measured range | Parameterizable |
Voltage measurement | Current-linear or customer- specific |
Input range/min. span | |
- Devices with 7NG3242-xxxx4
| -12 μA ... +100 μA/0.4 μA |
- Devices with 7NG3242-xxxx5
| -120 μA ... +1000 μA/4 μA |
- Devices with 7NG3242-xxxx6
| -1.2 mA ... +10 mA 0.04 mA |
- Devices with 7NG3242-xxxx7or 7NG3242-xxxx 0 with U/I plug
| -12 mA ... +100 mA 0.4 mA |
- Devices with 7NG3242-xxxx8
| -120 mA ... +1000 mA 4 mA |
Sensor breakage monitoring | Not possible |
Output | |
Output signal | Load-independent direct current 0/4 ... 20 mA, can be switched to load-independent DC voltage 0/2 ... 10 V using plug-in jumpers. |
Current 0/4 ... 20 mA | |
| -0.5 ... +23.0 mA, continuously adjustable |
- Output range following sensor fault
| -0.5 ... +23.0 mA, continuously adjustable |
| ≤ 650 Ω |
| ≤ 30 V |
Voltage 0/2 ... 10 V | |
| -0.25 ... +10.75 V, continuously adjustable |
- Output range following sensor fault
| -0.25 ... +10.75 V, continuously adjustable |
| ≥ 1 kΩ |
| ≤ 10 nF |
| ≤ 100 mA (not permanently short-circuit-proof) |
| |
- Adjustable time constant T63
| 0 ... 100 s, in steps of 0.1 s |
- Current source/voltage source
| Continuously adjustable within the total operating range |
Sensor fault/limit signalling | By operation indicator, relay output or HART interface |
Operation indicator | Flashing signal |
| Flashing frequency 5 Hz |
| Flashing frequency 1 Hz |
Relay output | Either as NO or NC contact with 1 changeover contact |
| ≤ 150 W, ≤ 625 VA |
| ≤ 125 V DC, ≤ 250 V AC |
| ≤ DC 2.5 A |
Overrange | Signalling of sensor or line breakage and sensor short-circuit |
Limit monitoring | |
| 0 ... 10 s |
- Monitoring functions of limit module
| - Sensor fault (breakage and/or short-circuit)
- Lower and upper limit
- Window (combination of lower and upper limits)
- Limit and sensor fault detection can be combined
|
| Parameterizable between 0 and 100 % of measuring range |
Power supply | |
Universal power supply unit | 115/230 V AC/DC or 24 V AC/DC |
Tolerance range for power supply | |
| 80 ... 300 V DC; 90 ... 250 V AC |
| 18 ... 80 V DC; 20.4 ... 55.2 V AC (in each case interruption-resistant up to 20 ms in the complete tolerance range) |
Tolerance range for mains frequency | 47 ... 63 Hz |
Power consumption with | |
| ≤ 5 VA |
| ≤ 5 W |
| ≤ 5 VA |
| ≤ 5 W |
Electrical isolation | |
Electrically isolated circuits | Input, output, power supply and sensor fault/limit monitoring output are electrically isolated from one another. The HART interface is electrically connected to the output. |
Working voltage between all electrically isolated circuits | The voltage U eff between any two terminals must not exceed 300 V |
Measuring accuracy | |
Measurement error | |
- Error in the internal cold junction
| ≤ 3 °C ± 0,1 °C/10 °C (≤ 5.4 °F ± 0,18 °F/18 °F) |
- Error of external cold junction terminal 7NG3092-8AV
| ≤ 0.5 °C ± 0,1 °C/10 °C (≤ 0.9 °F ± 0.18 °F/18 °F) |
| See "Digital error" |
| ≤ 0.05 % of span in addition to digital error |
Influencing effects (referred to the digital output) | Compared to the max. span: |
| ≤ 0.08 %/10 °C (≤ 0.08 %/18 °F) ≤ 0.2 % in the range -10 ... +60 °C (14 ... 140 °F) |
| ≤ 0.1 %/year |
Influencing effects referred to the analog output IAN or UAN | Compared to the span: |
| ≤ 0.08 %/10°C (≤ 0.08 %/18 °F) ≤ 0.2 % in the range -10 ... +60 °C (14 ... 140 °F) |
| ≤ 0.05 %/10 V |
| ≤ 0.05 % with change from 50 ... 650 Ω |
| ≤ 0.1 % with change in load current from 0 … 10 mA |
- Long-term drift (start-of-scale value, span)
| ≤ 0.03 %/month |
Response time (T63without electrical damping) | ≤ 0.2 s |
Electromagnetic compatibility | According to EN 61 326 and NAMUR NE21 |
Certificate and approvals | |
ATEX | To DIN EN 50014: 1997, EN 50020: 1994 |
Intrinsic safety to EN 50 020 | |
| II (1) G D [EEx ia/ib ] IIB |
| II (1) G D [EEx ia/ib ] IIC |
EC-Type Examination Certificate | TÜV (German Technical Inspectorate) 01 ATEX 1675 |
Rated conditions | |
Installation conditions | |
Location (for devices with explosion protection) | |
| Outside the potentially explosive atmosphere |
| Within the potentially explosive atmosphere zone 1 (also in zone 0 in conjunction with the prescribed protection requirements for the sensor) |
Ambient conditions | |
Permissible ambient temperature | -25 ... +70 °C (-13 ... +158 °F) |
Permissible storage temperature | -40 ... +85 °C (-40 ... +185 °F) |
Climatic class | |
| 5 ... 95 %, no condensation |
Design | |
Weight | Approx. 0.24 kg (0.53 lb) |
Enclosure material | PBT, glass-fibre reinforced |
Degree of protection to IEC 529 | IP20 |
Degree of protection to VDE 0100 | Protection class I |
Type of installation | 35-mm top hat rail (1.38 inch) (DIN EN 50022) or 32-mm G-type rail (1.26 inch) (DIN EN 50035) |
Electrical connection / process connection | Screw plug connectors, max. 2.5 mm² (0.01 inch²) |
Parameterization interface | |
Protocol | HART, version 5.9 |
Load with connection of | |
| 230 ... 650 Ω |
| 230 ... 500 Ω |
Software for PC/laptop | SIMATIC PDM version V5.1 and later |