Resistance thermometer


Mã sản phẩm: 7MC...
Tên sản phẩm: Resistance thermometer




Selection of suitable materials for protective tube and neck tube

Do you have high temperatures, high pressures, aggressive media? Or are you temperature measurements taken in fast flowing media? We can help you and have the right solution. You even have a choice of mounting types. Whether flange, screwed gland or welded connection - for us it's no problem.

Following resistance thermometers are available:

  • Flue gas resistance thermometer
  • Low-pressure screw-in resistance thermometer
    • Without neck tube
    • With neck tube
  • High-pressure screw-in resistance thermometer
  • High-pressure screw-in resistance thermometer
  • Flange-type resistance thermometer
  • Resistance thermometer for damp rooms

The following temperature transmitters are available for installation in the connection head

  • SITRANS TH100
  • SITRANS TH200/TH300
  • SITRANS TH400
 


http://anphatautomation.com/SITRANS TR200
SITRANS TR200


Mã sản phẩm: 7NG3032-0JN00
Tên sản phẩm: SITRANS TR200




Input

 

Resistance thermometer

 

Measured variable

Temperature

Sensor type

 
  • To IEC 60751

Pt25 … Pt1000

  • To JIS C 1604; a=0.00392 K-1

Pt25 … Pt1000

  • To IEC 60751

Ni25 … Ni1000

  • Special type

over special characteristic (max. 30 points)

Sensor factor

0.25 ... 10 (adaptation of the basic type, e.g. Pt100 to version Pt25 ... Pt1000)

Units

°C or °F

Connection

 
  • Standard connection

1 resistance thermometer (RTD) in 2-wire, 3-wire or 4-wire system

  • Generation of average value

2 identical resistance thermometers in 2-wire system for generation of average temperature

  • Generation of difference

2 identical resistance thermometers (RTD) in 2-wire system (RTD 1 – RTD 2 or RTD 2 – RTD 1)

Interface

 
  • Two-wire system

Parameterizable line resistance ≤ 100 Ω (loop resistance)

  • Three-wire system

No balancing required

  • Four-wire system

No balancing required

Sensor current

≤ 0.45 mA

Response time T63

≤ 250 ms for 1 sensor with open-circuit monitoring

Open-circuit monitoring

Always active (cannot be disabled)

Short-circuit monitoring

can be switched off (value is adjustable)

Measuring range

Parameterizable (see table "Digital measuring errors")

Min. measured span

10 °C (18 °F)

Characteristic curve

Temperature-linear or special characteristic

Resistance-based sensors

 

Measured variable

Actual resistance

Sensor type

Resistance-based, potentiometers

Units

Ω

Connection

 
  • Normal connection

1 resistance-based sensor (R) in 2-wire, 3-wire or 4-wire system

  • Generation of average value

2 resistance-based sensors in 2-wire system for generation of average value

  • Generation of difference

2 resistance thermometers in 2-wire system 
(R1 – R2 or R2 – R1)

Interface

 
  • Two-wire system

Parameterizable line resistance ≤ 100 Ω (loop resistance)

  • Three-wire system

No balancing required

  • Four-wire system

No balancing required

Sensor current

≤ 0.45 mA

Response time T63

≤ 250 ms for 1 sensor with open-circuit monitoring

Open-circuit monitoring

Always active (cannot be disabled)

Short-circuit monitoring

can be switched off (value is adjustable)

Measuring range

Parameterizable, max. 0 ... 2200 Ω (see Table "Digital measuring errors")

Min. measured span

5 Ω ... 25 Ω (see Table "Digital measuring errors")

Characteristic curve

Resistance-linear or special characteristic

Thermocouples

 

Measured variable

Temperature

Sensor type (thermocouples)

 
  • Type B

Pt30Rh-Pt6Rh to DIN IEC 584

  • Type C

W5 %-Re acc. to ASTM 988

  • Type D

W3 %-Re acc. to ASTM 988

  • Type E

NiCr-CuNi to DIN IEC 584

  • Type J

Fe-CuNi to DIN IEC 584

  • Type K

NiCr-Ni to DIN IEC 584

  • Type L

Fe-CuNi to DIN 43710

  • Type N

NiCrSi-NiSi to DIN IEC 584

  • Type R

Pt13Rh-Pt to DIN IEC 584

  • Type S

Pt10Rh-Pt to DIN IEC 584

  • Type T

Cu-CuNi to DIN IEC 584

  • Type U

Cu-CuNi to DIN 43710

Units

°C or °F

Connection

 
  • Standard connection

1 thermocouple (TC)

  • Generation of average value

2 identical thermocouples (TC)

  • Generation of difference

2 identical thermocouples (TC) TC1 – TC2 or TC2 – TC1

Response time T63

≤ 250 ms for 1 sensor with open-circuit monitoring

Open-circuit monitoring

can be switched off

Cold junction compensation

 
  • Internal

With integrated Pt100 resistance thermometer

  • External

With external Pt100 IEC 60571 (2-wire or 3-wire connection)

  • External fixed

Cold junction temperature can be set as fixed value

Measuring range

Parameterizable (see table "Digital measuring errors")

Min. measured span

Min. 50 ... 100 °C (90 ... 180 °F) (see table "Digital measuring errors")

Characteristic curve

Temperature-linear or special characteristic

mV sensor

 

Measured variable

DC voltage

Sensor type

DC voltage source (DC voltage source possible over an externally connected resistor)

Units

mV

Response time T63

≤ 250 ms for 1 sensor with open-circuit monitoring

Open-circuit monitoring

can be switched off

Measuring range

Parameterizable max. -100 … 1100 mV

 


http://anphatautomation.com/SITRANS TR300
SITRANS TR300


Mã sản phẩm: 7NG3033-0JN00
Tên sản phẩm: SITRANS TR300




Input

 

Resistance thermometer

 

Measured variable

Temperature

Sensor type

 
  • to IEC 60751

Pt25 to Pt1000

  • to JIS C 1604; a=0.00392 K-1

Pt25 to Pt1000

  • to IEC 60751

Ni25 to Ni1000

  • Special type

Over special characteristic (max. 30 points)

Sensor factor

0.25 ... 10 (adaptation of the basic type, e.g. Pt100 to version Pt25 ... Pt1000)

Units

°C or °F

Connection

 
  • Standard connection

1 resistance thermometer (RTD) in 2-wire, 3-wire or 4-wire system

  • Generation of average value

2 identical resistance thermometers in 2-wire system for generation of average temperature

  • Generation of difference

2 identical resistance thermometers (RTD) in 2-wire system (RTD 1 – RTD 2 or RTD 2 – RTD 1)

Interface

 
  • Two-wire system

Parameterizable line resistance ≤ 100 Ω (loop resistance)

  • Three-wire system

No balancing required

  • Four-wire system

No balancing required

Sensor current

≤ 0.45 mA

Response time T63

≤ 250 ms for 1 sensor with open-circuit monitoring

Open-circuit monitoring

Always active (Cannot switched off)

Short-circuit monitoring

Can be switched off (value is adjustable)

Range

Parameterizable (see table "Digital measuring errors")

Min. measured span

10 °C (18 °F)

Characteristic

Temperature-linear or special characteristic

Resistance-based sensors

 

Measured variable

Actual resistance

Sensor type

Resistance-based, potentiometers

Units

Ω

Connection

 
  • Normal connection

1 resistance-based sensor (R) in 2-wire, 3-wire or 4-wire system

  • Generation of average value

2 resistance-based sensors in 2-wire system for generation of average value

  • Generation of difference

2 resistance thermometers in 2-wire system 
(R1 – R2 or R2 – R1)

Interface

 
  • Two-wire system

Parameterizable line resistance ≤ 100 Ω (loop resistance)

  • Three-wire system

No balancing required

  • Four-wire system

No balancing required

Sensor current

≤ 0.45 mA

Response time T63

≤ 250 ms for 1 sensor with open-circuit monitoring

Open-circuit monitoring

Always active (cannot switched off)

Short-circuit monitoring

Can be switched off (value is adjustable)

Range

Parameterizable, max. 0 ... 2200 Ω (see Table "Digital measuring errors")

Min. measured span

5 Ω ... 25 Ω (see Table "Digital measuring errors")

Characteristic

Resistance-linear or special characteristic

Thermocouple elements

 

Measured variable

Temperature

Sensor type (thermocouples)

 
  • Type B

Pt30Rh-Pt6Rh to DIN IEC 584

  • Type C

W5 %-Re to ASTM 988

  • Type D

W3 %-Re to ASTM 988

  • Type E

NiCr-CuNi to DIN IEC 584

  • Type J

Fe-CuNi to DIN IEC 584

  • Type K

NiCr-Ni to DIN IEC 584

  • Type L

Fe-CuNi to DIN 43710

  • Type N

NiCrSi-NiSi to DIN IEC 584

  • Type R

Pt13Rh-Pt to DIN IEC 584

  • Type S

Pt10Rh-Pt to DIN IEC 584

  • Type T

Cu-CuNi to DIN IEC 584

  • Type U

Cu-CuNi to DIN 43710

Units

°C or °F

Connection

 
  • Standard connection

1 thermocouple (TC)

  • Generation of average value

2 thermocouples (TC)

  • Generation of difference

2 thermocouples (TC) TC1 – TC2 or TC2 – TC1

Response time T63

≤ 250 ms for 1 sensor with open-circuit monitoring

Open-circuit monitoring

Can be switched off

Cold junction compensation

 
  • Internal

With integrated Pt100 resistance thermometer

  • External

With external Pt100 IEC 60571 (2-wire or 3-wire connection)

  • External fixed

Cold junction temperature can be set as fixed value

Range

Parameterizable (see table "Digital measuring errors")

Min. measured span

Min. 50 ... 199 °C (90 ... 180 °F) (see table "Digital measuring errors")

Characteristic

Temperature-linear or special characteristic

mV Sensor

 

Measured variable

DC voltage

Sensor type

DC voltage source (DC voltage source possible over an externally connected resistor)

Units

mV

Response time T63

≤ 250 ms for 1 sensor with open-circuit monitoring

Open-circuit monitoring

Can be switched off

Short-circuit monitoring

Can be switched off (value is adjustable)

Range

Parameterizable max. -100 … 1100 mV

Min. measured span

2 mV or 20 mV

Overload capacity of the input

-1.5 ... +3.5 V DC

Input resistance

≥ 1 MΩ

Characteristic

Voltage-linear or special characteristic

Output

 

Output signal

4 ... 20 mA, 2-wire
Communication acc. to HART Rev. 5.9

Power supply

11 ... 35 V DC (to 30 V with EEx)

Max. load

(Uaux – 11 V)/0.023 A

Overrange

3.6 ... 23 mA, continuously adjustable (default range: 3.84 ... 20.5 mA)

Error signal (e.g. in the event of sensor breakage)

3.6 ... 23 mA, continuously adjustable (default value: 22.8 mA)

Sample cycle

0.25 s nominal

Damping

Software filter 1st order 0 ... 30 s (parameterizable)

Protection

Against reversed polarity

Electrically isolated

Input against output (1 kVeff)

Measuring accuracy

 

Digital measuring errors

See Table "Digital measuring errors"

Reference conditions

 
  • Power supply

24 V ± 1 %

  • Load

500 Ω

  • Storage temperature

23 °C

  • Warming-up time

> 5 min

Error in the analog ouput (digital/analog converter)

< 0.1 % of span

Error due to internal cold junction

< 0.55 °C (0.9 °F)

Temperature effect

< 0.1 % der max. span/10°C (18 °F)

Power supply effect

< 0.005 % of span/V

Effect of load impedance

< 0.012 % of span/100 Ω

Long-term drift

 
  • in the first month

< 0.02 % of max. span

  • after one year

< 0.03 % of max. span

  • after 5 years

< 0.04 % of max. span

Rated conditions

 

Ambient temperature

 

Storage temperature

-40 ... +85 °C (-40 ... 185 °F)

Functional temperature

-40 ... +85 °C (-40 ... 185 °F)

Relative humidity

< 98 %, with condensation

Electromagnetic compatibility

acc. to DIN EN 61326 and NAMUR NE21

Construction

 

Material

Plastic, electronic module potted

Approx. weight

122 g (0.27 lb)

Dimensions

See "Dimension drawings"

Cross-section of cables

Max. 2.5 mm² (AWG 13)

Degree of protection to EN 60529

 
  • Enclosure

IP40

  • Terminals

IP00

Certificate and approvals

 

Explosion protection ATEX

 

EC type test certificate

PTB 07 ATEX 2032X

  • "Intrinsic safety" type of protection

II 2(1) G Ex ia/ib IIC T6/T4

II 3(1) G Ex ia/ic IIC T6/T4

II 2(1) D Ex iaD/ibD 20/21 T115 °C

  • Type of protection, "equipment has limited energy"

II 3 G Ex nL IIC T6/T4

  • Type of protection, "equipment is non-arcing"

II 3 G Ex nA IIC T6/T4

Software requirements for SIPROM T

 

PC operating system:

Windows ME, 2000 and XP; also Windows 95, 98 and 98 SE, but only in connection with RS 232 modem.


Factory setting:

  • Pt100 (IEC 751) with three-wire circuit
  • Measuring range: 0 ... 100 °C (32 ... 212 °F)
  • Fault current: 22.8 mA
  • Sensor offset: 0 °C (0 °F)
  • Damping 0.0 s

Digital measuring errors

Resistance thermometer

input

Range

Min. measured span

Digital accuracy

 

°C (°F)

°C

(°F)

°C

(°F)

to IEC 60751

     

Pt25

-200 ... +850 (-328 ... +1562)

10

(18)

0.2

(0.36)

Pt50

-200 ... +850 (-328 ... +1562)

10

(18)

0.15

(0.27)

Pt100 ... Pt200

-200 ... +850 (-328 ... +1562)

10

(18)

0.1

(0.18)

Pt500

-200 ... +850 (-328 ... +1562)

10

(18)

0.15

(0.27)

Pt1000

-200 ... +350 (-328 ... +662)

10

(18)

0.15

(0.27)

to JIS C1604-81

     

Pt25

-200 ... +649 (-328 ... +1200)

10

(18)

0.2

(0.36)

Pt50

-200 ... +649 (-328 ... +1200)

10

(18)

0.15

(0.27)

Pt100 ... Pt200

-200 ... +649 (-328 ... +1200)

10

(18)

0.1

(0.18)

Pt500

-200 ... +649 (-328 ... +1200)

10

(18)

0.15

(0.27)

Pt1000

-200 ... +350 (-328 ... +662)

10

(18)

0.15

(0.27)

Ni 25 to Ni1000

-60 ... +250 (-76 ... +482)

10

(18)

0.1

(0.18)


Resistance-based sensors

Input

Range

Min. measured span

Digital accuracy

 

Ω

Ω

Ω

Resistance

0 ... 390

5

0.05

Resistance

0 ... 2200

25

0.25


Thermocouples

Input

Measuring range

Min. measured span

Digital accuracy

 

°C

(°F)

°C

(°F)

°C

(°F)

Type B

0 ... 1820

(32 ... 3308)

100

(180)

21)

(3.60)1)

Type C (W5)

0 ... 2300

(32 ... 4172)

100

(180)

2

(3.60)

Type D (W3)

0 ... 2300

(32 ... 4172)

100

(180)

12)

(1.80)2)

Type E

-200 ... +1000

(-328 ... +1832)

50

(90)

1

(1.80)

Type J

-210 ... +1200

(-346 ... +2192)

50

(90)

1

(1.80)

Type K

-230 ... +1370

(-382 ... +2498)

50

(90)

1

(1.80)

Type L

-200 ... +900

(-328 ... +1652)

50

(90)

1

(1.80)

Type N

-200 ... +1300

(-328 ... +2372)

50

(90)

1

(1.80)

Type R

-50 ... +1760

(-58 ... +3200)

100

(180)

2

(3.60)

Type S

-50 ... +1760

(-58 ... +3200)

100

(180)

2

(3.60)

Type T

-200 ... +400

(-328 ... +752)

40

(72)

1

(1.80)

Type U

-200 ... +600

(-328 ... +1112)

50

(90)

2

(3.60)


1) The digital accuracy in the range 0 to 300 °C (32 to 572 °F) is 3 °C (5.4 °F).

2) The digital accuracy in the range 1750 to 2300 °C (3182 to 4172 °F) is 2 °C (3.6 °F).

mV Sensor

input

Range

Min. measured span

Digital accuracy

 

mV

mV

μV

mV Sensor

-10 ... +70

2

40

mV Sensor

-100 ... +1100

20

400


The digital accuracy is the accuracy after the analog/digital conversion including linearization and calculation of the measured value.

An additional error is generated in the output current 4 to 20 mA as a result of the digital/analog conversion of 0.1 % of the set span (digital-analog error).

The total error under reference conditions at the analog output is the sum from the digital error and the digital-analog error (poss. with the addition of cold junction errors in the case of thermocouple measurements). 


http://anphatautomation.com/SITRANS TH300
SITRANS TH300


Mã sản phẩm: 7NG3212-0NN00
Tên sản phẩm: SITRANS TH300




Input

 

Resistance thermometer

 

Measured variable

Temperature

Sensor type

 
  • To IEC 60751

Pt25 … Pt1000

  • To JIS C 1604; a = 0.00392 K-1

Pt25 … Pt1000

  • To IEC 60751

Ni25 … Ni1000

  • Special type

over special characteristic (max. 30 points)

Sensor factor

0.25 ... 10 (adaptation of the basic type, e.g. Pt100 to version Pt25 ... Pt1000)

Units

°C or °F

Connection

 
  • Standard connection

1 resistance thermometer (RTD) in 2-wire, 3-wire or 4-wire system

  • Generation of average value

2 identical resistance thermometers in 2-wire system for generation of average temperature

  • Generation of difference

2 identical resistance thermometers (RTD) in 2-wire system (RTD 1 – RTD 2 or RTD 2 – RTD 1)

Interface

 
  • Two-wire system

Parameterizable line resistance ≤ 100 Ω (loop resistance)

  • Three-wire system

No balancing required

  • Four-wire system

No balancing required

Sensor current

≤ 0.45 mA

Response time

≤ 250 ms for 1 sensor with open-circuit monitoring

Open-circuit monitoring

can be switched off

Short-circuit monitoring

can be switched off (value is adjustable)

Measuring range

Parameterizable (see table "Digital measuring errors")

Min. measured span

10 °C (18 °F)

Characteristic curve

Temperature-linear or special characteristic

Resistance-based sensors

 

Measured variable

Actual resistance

Sensor type

Resistance-based, potentiometers

Units

Ω

Connection

 
  • Normal connection

1 resistance-based sensor (R) in 2-wire, 3-wire or 4-wire system

  • Generation of average value

2 resistance-based sensors in 2-wire system for generation of average value

  • Generation of difference

2 resistance thermometers in 2-wire system 
(R1 – R2 or R2 – R1)

Interface

 
  • Two-wire system

Parameterizable line resistance ≤ 100 Ω (loop resistance)

  • Three-wire system

No balancing required

  • Four-wire system

No balancing required

Sensor current

≤ 0.45 mA

Response time

≤ 250 ms for 1 sensor with open-circuit monitoring

Open-circuit monitoring

can be switched off

Short-circuit monitoring

can be switched off (value is adjustable)

Measuring range

Parameterizable, max. 0 ... 2200 Ω (see Table "Digital measuring errors")

Min. measured span

5 Ω ... 25 Ω (see Table "Digital measuring errors")

Characteristic curve

Resistance-linear or special characteristic

Thermocouples

 

Measured variable

Temperature

Sensor type (thermocouples)

 
  • Type B

Pt30Rh-Pt6Rh to DIN IEC 584

  • Type C

W5 %-Re acc. to ASTM 988

  • Type D

W3 %-Re acc. to ASTM 988

  • Type E

NiCr-CuNi to DIN IEC 584

  • Type J

Fe-CuNi to DIN IEC 584

  • Type K

NiCr-Ni to DIN IEC 584

  • Type L

Fe-CuNi to DIN 43710

  • Type N

NiCrSi-NiSi to DIN IEC 584

  • Type R

Pt13Rh-Pt to DIN IEC 584

  • Type S

Pt10Rh-Pt to DIN IEC 584

  • Type T

Cu-CuNi to DIN IEC 584

  • Type U

Cu-CuNi to DIN 43710

Units

°C or °F

Connection

 
  • Standard connection

1 thermocouple (TC)

  • Generation of average value

2 thermocouples (TC)

  • Generation of difference

2 thermocouples (TC) TC1 – TC2 or TC2 – TC1)

Response time

≤ 250 ms for 1 sensor with open-circuit monitoring

Open-circuit monitoring

can be switched off

Cold junction compensation

 
  • Internal

With integrated Pt100 resistance thermometer

  • External

With external Pt100 IEC 60571 (2-wire or 3-wire connection)

  • External fixed

Cold junction temperature can be set as fixed value

Measuring range

Parameterizable (see table "Digital measuring errors")

Min. measured span

Min. 50 ... 199 °C (90 ... 180 °F) (see table "Digital measuring errors")

Characteristic curve

Temperature-linear or special characteristic

mV sensor

 

Measured variable

DC voltage

Sensor type

DC voltage source (DC voltage source possible over an externally connected resistor)

Units

mV

Response time

≤ 250 ms for 1 sensor with open-circuit monitoring

Open-circuit monitoring

can be switched off

Short-circuit monitoring

can be switched off (value is adjustable)

Measuring range

-10 ... +70 mV
-100 … +1100 mV

Min. measured span

2 mV or 20 mV

Overload capability of the input

-1.5 ... +3.5 V DC

Input resistance

≥ 1 MΩ

Characteristic curve

Voltage-linear or special characteristic

Output

 

Output signal

4 ... 20 mA, 2-wire with communication acc. to HART Rev. 5.9

Auxiliary power supply

11 ... 35 V DC (to 30 V with EEx)

Max. load

(Uaux – 11 V)/0.023 A

Overrange

3.6 ... 23 mA, infinitely adjustable (default range: 3.80 mA ... 20.50 mA)

Error signal (e.g. in the event of sensor breakage)

3.6 ... 23 mA, infinitely adjustable (default value: 22.8 mA)

Sample cycle

0.25 s nominal

Damping

Software filter 1st order 0 ... 30 s (parameterizable)

Protection

Against reversed polarity

Electrically isolated

Input against output (1 kVeff)

Measuring accuracy

 

Digital measuring errors

See Table "Digital measuring errors"

Reference conditions

 
  • Auxiliary power supply

24 V ± 1 %

  • Load

500 Ω

  • Ambient temperature

23 °C

  • Warming-up time

> 5 min

Error in the analog output (digital/analog converter)

< 0.1 % of span

Error due to internal cold junction

< 0.5 °C (0.9 °F)

Temperature effect

< 0.1 % of max. span/10 °C (18 °F)

Auxiliary power supply effect

< 0.005 % of span/V

Effect of load impedance

< 0.012 % of span/100 Ω

Long-term drift

 
  • In the first month

< 0.02 % of max. span

  • After one year

< 0.03 % of max. span

  • After 5 years

< 0.04 % of max. span

Conditions of use

 

Ambient conditions

 

Ambient temperature range

-40 ... +85 °C (-40 ... 185 °F)

Storage temperature range

-40 ... +85 °C (-40 ... 185 °F)

Relative humidity

< 98 %, with condensation

Electromagnetic compatibility

acc. to EN 61326 and NE21

Construction

 

Material

Molded plastic

Weight

50 g (0.11 lb)

Dimensions

See "Dimensional drawings"

Cross-section of cables

Max. 2.5 mm² (AWG 13)

Degree of protection to IEC 60529

 
  • Enclosure

IP40

  • Terminals

IP00

Certificates and approvals

 

Explosion protection ATEX

 

EC type test certificate

PTB 05 ATEX 2040X

  • "Intrinsic safety" type of protection

II 1 G Ex ia IIC T6/T4
II 2(1) G Ex ib/ia IIC T6/T4

  • "Operating equipment that is non-ignitable and has limited energy" type of protection

II 3 G Ex nL IIC T6/T4
II 3 G Ex nA IIC T6/T4

Explosion protection: FM for USA

 
  • FM approval

FM 3024169

  • Degree of protection

IS/Cl I, II, III/Div 1/GP ABCDEFG T6, T5, T4

IS/Cl I/ZN 0/AEx ia IIC T6, T5, T4

NI/Cl I, II, III/Div 2/GP ABCDFG T6, T5, T4

NI/Cl I/ZN 2/IIC T6, T5, T4

Explosion protection to FM for Canada (cFMUS)

 
  • FM approval

FM 3024169C

  • Degree of protection

IS/Cl I/ZN 0/Ex ia IIC T6, T5, T4

NI/Cl I/ZN 2/Ex nAL IIC T6, T5, T4


Factory setting:

  • Pt100 (IEC 751) with 3-wire circuit
  • Measuring range: 0 ... 100 °C (32 ... 212 °F)
  • Fault current: 22.8 mA
  • Sensor offset: 0 °C (0 °F)
  • Damping 0.0 s

Digital measuring errors

Resistance thermometer

Input

Measuring range

Min. measured span

Digital accuracy

 

°C (°F)

°C

(°F)

°C

(°F)

to IEC 60751

     

Pt25

-200 ... +850 (-328 ... +1562)

10

(18)

0.2

(0.36)

Pt50

-200 ... +850 (-328 ... +1562)

10

(18)

0.15

(0.27)

Pt100 ... Pt200

-200 ... +850 (-328 ... +1562)

10

(18)

0.1

(0.18)

Pt500

-200 ... +850 (-328 ... +1562)

10

(18)

0.15

(0.27)

Pt1000

-200 ... +350 (-328 ... +662)

10

(18)

0.15

(0.27)

to JIS C1604-81

     

Pt25

-200 ... +649 (-328 ... +1200)

10

(18)

0.2

(0.36)

Pt50

-200 ... +649 (-328 ... +1200)

10

(18)

0.15

(0.27)

Pt100 ... Pt200

-200 ... +649 (-328 ... +1200)

10

(18)

0.1

(0.18)

Pt500

-200 ... +649 (-328 ... +1200)

10

(18)

0.15

(0.27)

Pt1000

-200 ... +350 (-328 ... +662)

10

(18)

0.15

(0.27)

Ni 25 to Ni1000

-60 ... +250 (-76 ... +482)

10

(18)

0.1

(0.18)


Resistance-based sensors

Input

Measuring range

Min. measured span

Digital accuracy

 

Ω

Ω

Ω

Resistance

0 ... 390

5

0.05

Resistance

0 ... 2200

25

0.25


Thermocouples

Input

Measuring range

Min. measured span

Digital accuracy

 

°C

(°F)

°C

(°F)

°C

(°F)

Type B

0 ... 1820

(32 ... 3308)

100

(180)

21)

(3.60)1)

Type C (W5)

0 ... 2300

(32 ... 4172)

100

(180)

2

(3.60)

Type D (W3)

0 ... 2300

(32 ... 4172)

100

(180)

12)

(1.80)2)

Type E

-200 ... +1000

(-328 ... +1832)

50

(90)

1

(1.80)

Type J

-210 ... +1200

(-346 ... +2192)

50

(90)

1

(1.80)

Type K

-230 ... +1370

(-382 ... +2498)

50

(90)

1

(1.80)

Type L

-200 ... +900

(-328 ... +1652)

50

(90)

1

(1.80)

Type N

-200 ... +1300

(-328 ... +2372)

50

(90)

1

(1.80)

Type R

-50 ... +1760

(-58 ... +3200)

100

(180)

2

(3.60)

Type S

-50 ... +1760

(-58 ... +3200)

100

(180)

2

(3.60)

Type T

-200 ... +400

(-328 ... +752)

40

(72)

1

(1.80)

Type U

-200 ... +600

(-328 ... +1112)

50

(90)

2

(3.60)


1) The digital accuracy in the range 0 to 300 °C (32 to 572 °F) is 3 °C (5.4 °F).

2) The digital accuracy in the range 1750 to 2300 °C (3182 to 4172 °F) is 2 °C (3.6 °F).

mV sensor

Input

Measuring range

Min. measured span

Digital accuracy

 

mV

mV

μV

mV sensor

-10 ... +70

2

40

mV sensor

-100 ... +1100

20

400


The digital accuracy is the accuracy after the analog/digital conversion including linearization and calculation of the measured value.

An additional error is generated in the output current 4 to 20 mA as a result of the digital/analog conversion of 0,1 % of the set span (digital-analog error).

The total error under reference conditions at the analog output is the sum from the digital error and the digital-analog error (poss. with the addition of cold junction errors in the case of thermocouple measurements). 


http://anphatautomation.com/SITRANS TH200
SITRANS TH200


Mã sản phẩm: 7NG3211-1NN00
Tên sản phẩm: SITRANS TH200




Input

 

Resistance thermometer

 

Measured variable

Temperature

Sensor type

 
  • To IEC 60751

Pt25 … Pt1000

  • To JIS C 1604; a = 0.00392 K-1

Pt25 … Pt1000

  • To IEC 60751

Ni25 … Ni1000

  • Special type

over special characteristic (max. 30 points)

Sensor factor

0.25 ... 10 (adaptation of the basic type, e.g. Pt100 to version Pt25 ... Pt1000)

Units

°C or °F

Connection

 
  • Standard connection

1 resistance thermometer (RTD) in 2-wire, 3-wire or 4-wire system

  • Generation of average value

2 identical resistance thermometers in 2-wire system for generation of average temperature

  • Generation of difference

2 identical resistance thermometers (RTD) in 2-wire system (RTD 1 – RTD 2 or RTD 2 – RTD 1)

Interface

 
  • Two-wire system

Parameterizable line resistance ≤ 100 Ω (loop resistance)

  • Three-wire system

No balancing required

  • Four-wire system

No balancing required

Sensor current

≤ 0.45 mA

Response time

≤ 250 ms for 1 sensor with open-circuit monitoring

Open-circuit monitoring

can be switched off

Short-circuit monitoring

can be switched off (value is adjustable)

Measuring range

Parameterizable (see table "Digital measuring errors")

Min. measured span

10 °C (18 °F)

Characteristic curve

Temperature-linear or special characteristic

Resistance-based sensors

 

Measured variable

Actual resistance

Sensor type

Resistance-based, potentiometers

Units

Ω

Connection

 
  • Normal connection

1 resistance-based sensor (R) in 2-wire, 3-wire or 4-wire system

  • Generation of average value

2 resistance-based sensors in 2-wire system for generation of average value

  • Generation of difference

2 resistance thermometers in 2-wire system 
(R1 – R2 or R2 – R1)

Interface

 
  • Two-wire system

Parameterizable line resistance ≤ 100 Ω (loop resistance)

  • Three-wire system

No balancing required

  • Four-wire system

No balancing required

Sensor current

≤ 0.45 mA

Response time

≤ 250 ms for 1 sensor with open-circuit monitoring

Open-circuit monitoring

can be switched off

Short-circuit monitoring

can be switched off (value is adjustable)

Measuring range

Parameterizable, max. 0 ... 2200 Ω (see Table "Digital measuring errors")

Min. measured span

5 Ω ... 25 Ω (see Table "Digital measuring errors")

Characteristic curve

Resistance-linear or special characteristic

Thermocouples

 

Measured variable

Temperature

Sensor type (thermocouples)

 
  • Type B

Pt30Rh-Pt6Rh to DIN IEC 584

  • Type C

W5 %-Re acc. to ASTM 988

  • Type D

W3 %-Re acc. to ASTM 988

  • Type E

NiCr-CuNi to DIN IEC 584

  • Type J

Fe-CuNi to DIN IEC 584

  • Type K

NiCr-Ni to DIN IEC 584

  • Type L

Fe-CuNi to DIN 43710

  • Type N

NiCrSi-NiSi to DIN IEC 584

  • Type R

Pt13Rh-Pt to DIN IEC 584

  • Type S

Pt10Rh-Pt to DIN IEC 584

  • Type T

Cu-CuNi to DIN IEC 584

  • Type U

Cu-CuNi to DIN 43710

Units

°C or °F

Connection

 
  • Standard connection

1 thermocouple (TC)

  • Generation of average value

2 thermocouples (TC)

  • Generation of difference

2 thermocouples (TC) TC1 – TC2 or TC2 – TC1)

Response time

≤ 250 ms for 1 sensor with open-circuit monitoring

Open-circuit monitoring

can be switched off

Cold junction compensation

 
  • Internal

With integrated Pt100 resistance thermometer

  • External

With external Pt100 IEC 60571 (2-wire or 3-wire connection)

  • External fixed

Cold junction temperature can be set as fixed value

Measuring range

Parameterizable (see table "Digital measuring errors")

Min. measured span

Min. 50 ... 100 °C (90 ... 180 °F) (see table "Digital measuring errors")

Characteristic curve

Temperature-linear or special characteristic

mV sensor

 

Measured variable

DC voltage

Sensor type

DC voltage source (DC voltage source possible over an externally connected resistor)

Units

mV

Response time

≤ 250 ms for 1 sensor with open-circuit monitoring

Open-circuit monitoring

can be switched off

Short-circuit monitoring

can be switched off (value is adjustable)

Measuring range

-10 ... +70 mV
-100   +1100 mV

Min. measured span

2 mV or 20 mV

Overload capability of the input

-1.5 ... +3.5 V DC

Input resistance

≥ 1 MΩ

Characteristic curve

Voltage-linear or special characteristic

Output

 

Output signal

4 ... 20 mA, 2-wire

Auxiliary power supply

11 ... 35 V DC (to 30 V with EEx)

Max. load

(Uaux – 11 V)/0.023 A

Overrange

3.6 ... 23 mA, infinitely adjustable (default range: 3.80 mA ... 20.50 mA)

Error signal (e.g. in the event of sensor breakage)

3.6 ... 23 mA, infinitely adjustable (default value: 22.8 mA)

Sample cycle

0.25 s nominal

Damping

Software filter 1st order 0 ... 30 s (parameterizable)

Protection

Against reversed polarity

Electrically isolated

Input against output (1 kVeff)

Measuring accuracy

 

Digital measuring errors

See Table "Digital measuring errors"

Reference conditions

 
  • Auxiliary power supply

24 V ± 1 %

  • Load

500 Ω

  • Ambient temperature

23 °C

  • Warming-up time

> 5 min

Error in the analog output (digital/analog converter)

< 0.1 % of span

Error due to internal cold junction

< 0.5 °C (0.9 °F)

Temperature effect

< 0.1 % of max. span/10 °C (18 °F)

Auxiliary power supply effect

< 0.005 % of span/V

Effect of load impedance

< 0.012 % of span/100 Ω

Long-term drift

 
  • In the first month

< 0.02 % of max. span

  • After one year

< 0.03 % of max. span

  • After 5 years

< 0.04 % of max. span

Conditions of use

 

Ambient conditions

 

Ambient temperature range

-40 ... +85 °C (-40 ... 185 °F)

Storage temperature range

-40 ... +85 °C (-40 ... 185 °F)

Relative humidity

< 98 %, with condensation

Electromagnetic compatibility

acc. to EN 61326 and NE21

Construction

 

Material

Molded plastic

Weight

50 g (0.11 lb)

Dimensions

See "Dimensional drawings"

Cross-section of cables

Max. 2.5 mm² (AWG 13)

Degree of protection to IEC 60529

 
  • Enclosure

IP40

  • Terminals

IP00

Certificates and approvals

 

Explosion protection ATEX

 

EC type test certificate

PTB 05 ATEX 2040X

  • "Intrinsic safety" type of protection

II 1 G Ex ia IIC T6/T4
II 2(1) G Ex ib/ia IIC T6/T4

  • "Operating equipment that is non-ignitable and has limited energy" type of protection

II 3 G Ex nL IIC T6/T4
II 3 G Ex nA IIC T6/T4

Explosion protection: FM for USA

 
  • FM approval

FM 3024169

  • Degree of protection

IS/Cl I, II, III/Div 1/GP ABCDEFG T6, T5, T4

IS/Cl I/ZN 0/AEx ia IIC T6, T5, T4

NI/Cl I, II, III/Div 2/GP ABCDFG T6, T5, T4

NI/Cl I/ZN 2/IIC T6, T5, T4

Explosion protection to FM for Canada (cFMUS)

 
  • FM approval

FM 3024169C

  • Degree of protection

IS/Cl I/ZN 0/Ex ia IIC T6, T5, T4

NI/Cl I/ZN 2/Ex nAL IIC T6, T5, T4

Software requirements for SIPROM T

 

PC operating system

Windows ME, 2000 and XP; also Windows 95, 98 and 98 SE, but only in connection with RS 232 modem.


Factory setting:

  • Pt100 (IEC 751) with 3-wire circuit
  • Measuring range: 0 ... 100 °C (32 ... 212 °F)
  • Fault current: 22.8 mA
  • Sensor offset: 0 °C (0 °F)
  • Damping 0.0 s

Digital measuring errors

Resistance thermometer

Input

Measuring range

Min. measured span

Digital accuracy

 

°C (°F)

°C

(°F)

°C

(°F)

to IEC 60751

     

Pt25

-200 ... +850 (-328 ... +1562)

10

(18)

0.2

(0.36)

Pt50

-200 ... +850 (-328 ... +1562)

10

(18)

0.15

(0.27)

Pt100 ... Pt200

-200 ... +850 (-328 ... +1562)

10

(18)

0.1

(0.18)

Pt500

-200 ... +850 (-328 ... +1562)

10

(18)

0.15

(0.27)

Pt1000

-200 ... +350 (-328 ... +662)

10

(18)

0.15

(0.27)

to JIS C1604-81

     

Pt25

-200 ... +649 (-328 ... +1200)

10

(18)

0.2

(0.36)

Pt50

-200 ... +649 (-328 ... +1200)

10

(18)

0.15

(0.27)

Pt100 ... Pt200

-200 ... +649 (-328 ... +1200)

10

(18)

0.1

(0.18)

Pt500

-200 ... +649 (-328 ... +1200)

10

(18)

0.15

(0.27)

Pt1000

-200 ... +350 (-328 ... +662)

10

(18)

0.15

(0.27)

Ni 25 to Ni1000

-60 ... +250 (-76 ... +482)

10

(18)

0.1

(0.18)


Resistance-based sensors

Input

Measuring range

Min. measured span

Digital accuracy

 

Ω

Ω

Ω

Resistance

0 ... 390

5

0.05

Resistance

0 ... 2200

25

0,25


Thermocouples

Input

Measuring range

Min. measured span

Digital accuracy

 

°C

(°F)

°C

(°F)

°C

(°F)

Type B

0 ... 1820

(32 ... 3308)

100

(180)

21)

(3.60)1)

Type C (W5)

0 ... 2300

(32 ... 4172)

100

(180)

2

(3.60)

Type D (W3)

0 ... 2300

(32 ... 4172)

100

(180)

12)

(1.80)2)

Type E

-200 ... +1000

(-328 ... +1832)

50

(90)

1

(1.80)

Type J

-210 ... +1200

(-346 ... +2192)

50

(90)

1

(1.80)

Type K

-230 ... +1370

(-382 ... +2498)

50

(90)

1

(1.80)

Type L

-200 ... +900

(-328 ... +1652)

50

(90)

1

(1.80)

Type N

-200 ... +1300

(-328 ... +2372)

50

(90)

1

(1.80)

Type R

-50 ... +1760

(-58 ... +3200)

100

(180)

2

(3.60)

Type S

-50 ... +1760

(-58 ... +3200)

100

(180)

2

(3.60)

Type T

-200 ... +400

(-328 ... +752)

40

(72)

1

(1.80)

Type U

-200 ... +600

(-328 ... +1112)

50

(90)

2

(3.60)


1) The digital accuracy in the range 0 to 300 °C (32 to 572 °F) is 3 °C (5.4 °F).

2) The digital accuracy in the range 1750 to 2300 °C (3182 to 4172 °F) is 2 °C (3.6 °F).

mV sensor

Input

Measuring range

Min. measured span

Digital accuracy

 

mV

mV

μV

mV sensor

-10 ... +70

2

40

mV sensor

-100 ... +1100

20

400


The digital accuracy is the accuracy after the analog/digital conversion including linearization and calculation of the measured value.

An additional error is generated in the output current 4 to 20 mA as a result of the digital/analog conversion of 0.1 % of the set span (digital-analog error).

The total error under reference conditions at the analog output is the sum from the digital error and the digital-analog error (poss. with the addition of cold junction errors in the case of thermocouple measurements). 


http://anphatautomation.com/SITRANS TH400, fieldbus transmitters
SITRANS TH400, fieldbus transmitters


Mã sản phẩm: 7NG3214/7NG3215
Tên sản phẩm: SITRANS TH400, fieldbus transmitters




Input

 

Analog-to-digital conversion

 
  • Measurement rate

< 50 ms

  • Resolution

24-bit

Resistance thermometer

 

Pt25 ... Pt1000 to IEC 60751/JIS C 1604

 
  • Measuring range

-200 ... +850 °C (-328 ... +1562 °F)

Ni25 ... Ni1000 to DIN 43760

 
  • Measuring range

-60 ... +250 °C (-76 ... +482 °F)

Cu10 ... Cu1000, α = 0.00427

 
  • Measuring range

-50 ... +200 °C (-58 ... +392 °F)

Line resistance per sensor cable

Max. 50 Ω

Sensor current

Nominal 0.2 mA

Sensor fault detection

 
  • Sensor break detection

Yes

  • Sensor short-circuit detection

Yes, < 15 Ω

Resistance-based sensors

 

Measuring range

0 Ω ... 10 kΩ

Line resistance per sensor cable

Max. 50 Ω

Sensor current

Nominal 0.2 mA

Sensor fault detection

 
  • Sensor break detection

Yes

  • Sensor short-circuit detection

Yes, < 15 Ω

Thermocouple

 

to IEC 584

Measuring range

  • Type B

400 ... 1820 °C (752 ... 3308 °F)

  • Type E

-100 ... +1000 °C (-148 ... +1832 °F)

  • Type J

-100 ... +1000 °C (-148 ... +1832 °F)

  • Type K

-100 ... +1200 °C (-148 ... +2192 °F)

  • Type N

-180 ... +1300 °C (-292 ... +2372 °F)

  • Type R

-50 ... +1760 °C (-58 ... +3200 °F)

  • Type S

-50 ... +1760 °C (-58 ... +3200 °F)

  • Type T

-200 ... +400 °C (-328 ... +752 °F)

to DIN 43710

 
  • Type L

-200 ... +900 °C (-328 ... +1652 °F)

  • Type U

-200 ... +600 °C (-328 ... +1112 °F)

to ASTM E988-90

 
  • Type W3

0 ... 2300 °C (32 ... +4172 °F)

  • Type W5

0 ... 2300 °C (32 ... +4172 °F)

External cold junction compensation

-40 ... +135 °C (-40 ... +275 °F)

Sensor fault detection

 
  • Sensor break detection

Yes

  • Sensor short-circuit detection

Yes, < 3 mV

  • Sensor current in the event of open-circuit monitoring

4 μA

mV sensor - voltage input

 

Measuring range

-800 ... +800 mV

Input resistance

10 MΩ

Output

 

Filter time (programmable)

0 ... 60 s

Update time

< 400 ms


Measuring accuracy

  

Accuracy is defined as the higher value of general values and basic values.

General values

  

Type of input

Absolute accuracy

Temperature coefficient

All

≤ ±0.05 % of measured value

≤ ±0.002 % of measured value / °C

Basic values

  

Type of input

Basic accuracy

Temperature coefficient

Pt100 and Pt1000

≤± 0.1 °C

≤± 0.002 °C / °C

Ni100

≤± 0.15 °C

≤± 0.002 °C / °C

Cu10

≤± 1.3 °C

≤± 0.02 °C / °C

Resistance-based sensors

≤± 0.05 °Ω

≤± 0.002 °Ω / °C

Voltage source

≤± 10 μV

≤± 0.2 % μV / °C

Thermocouple, type:
E, J, K, L, N, T, U

≤± 0.5 °C

≤± 0.01 °Ω / °C

Thermocouple, type:
B, R, S, W3, W5

≤± 1 °C

≤± 0.025 % °C / °C

Cold junction compensation

≤± 0.5 °C

 

Reference conditions

  

Warming-up time

30 s

 

Signal-to-noise ratio

Min. 60 dB

 

Calibration condition

20 ... 28 °C (68 ... 82 °F)

 

Conditions of use

 

Ambient conditions

 

Permissible ambient temperature

-40 ... +85 °C (-40 ... +185 °F)

Permissible storage temperature

-40 ... +85 °C (-40 ... +185 °F)

Relative humidity

≤ 98 %, with condensation

Electrically isolated

 
  • Without Ex

Input against output 1 kVeff

  • With Ex

Input against output 500 Veff

Mechanical testing

 
  • Vibrations (DIN class B) to

IEC 60068-2-6 and IEC 60068-2-64
4 g/2 ... 100 Hz

Electromagnetic compatibility

 

EMC noise voltage influence

< ±0.1 % of span

Extended EMC noise immunity:
NAMUR NE 21, criterion A, Burst

< ±1 % of span

EMC 2004/108/EC Emission and Noise Immunity to

EN 61326

Construction

 

Material

Molded plastic

Weight

55 g (0.12 lb)

Dimensions

See Dimensional drawings

Cross-section of cables

Max. 2.5 mm2 (AWG 13)

Degree of protection

 
  • Transmitter enclosure

IP40

  • Terminal

IP00

Auxiliary power supply

 

Power supply

 
  • Standard, Ex "nA", Ex "nL", NI

9.0 ... 32 V DC

  • ATEX, FM, UL and CSA

9.0 ... 30 V DC

  • In FISCO/FNICO installations

9.0 ... 17.5 V DC

Power consumption

< 11 mA

Max. increase in power consumption in the event of a fault

< 7 mA


Certificates and approvals

 

Explosion protection ATEX

 

EC type test certificate

KEMA 06 ATEX 0264 X

  • "Intrinsic safety" type of protection

II 1 GD EEx ia IIC T4 ... T6
T65 °C ... T105 °C

II 2(1) GD EEx ib [ia] IIC T4 ... T6
T65 °C ... T105 °C

EC type test certificate

KEMA 06 ATEX 0263 X

  • Type of protection for "equipment is non-arcing"

II 3 G EEx nA [nL] IIC T4 ... T6
II 3 G EEx nL IIC T4 ... T6

Explosion protection: FM for USA

 
  • FM approval

FM 3027985

  • Degree of protection
  • IS/Cl I/Div 1/Groups ABCD T4, T5, T6, FISCO
  • IS/Cl I/ZN 0/AEx ia, IIC T4, T5, T6, FISCO
  • NI/Cl I/Div 2/Groups ABCD T4, T5, T6, FNICO

Explosion protection CSA for Canada

 
  • CSA approval

CSA 1861385

  • Degree of protection
  • IS/Cl I/Div 1/Groups ABCD T4, T5, T6
  • Ex ia IIC T4/T5/T6
    Ex ib [ia] IIC T4/T5/T6
  • Cl I/Div 2/Groups ABCD, T4, T5, T6
  • Ex nA IIC T4/T5/T6
    Cl I/ZN 2/AEx nA II T4, T5, T6

Communication

 

Parameterization interface

 
  • PROFIBUS PA connection
 
  • Protocol

Profile 3.0

  • Address (for delivery)

126

  • FOUNDATION fieldbus connection
 
  • Protocol

FF protocol

  • Functionality

Basic or LAS

  • Version

ITK 4.6

  • Function blocks

2 x analog and 1 x PID

Factory setting

only for SITRANS TH400 PA

 

Sensor

Pt100 (IEC)

Type of connection

3-wire circuit

Unit

°C

Failure mode

Last valid value

Filter time

0 s

PA address

126

PROFIBUS Ident No.

Manufacturer-specific

only for SITRANS TH400 FF

 

Sensor

Pt100 (IEC)

Type of connection

3-wire circuit

Unit

°C

Failure mode

Last valid value

Filter time

0 s

Node address

22

 


http://anphatautomation.com/SITRANS TF2, digital display thermometer
SITRANS TF2, digital display thermometer


Mã sản phẩm: 7NG3140
Tên sản phẩm: SITRANS TF2, digital display thermometer




Measuring principle

 

Resistance thermometer

Pt100 class B acc. to DIN IEC 751

Input

 

Measured variable

Temperature

Max. measuring range

-50 °C ... +200 °C (-58 ... +392 °F)

Min. measured span

50 K (90 °F)

Output

 

Output signal

4 ... 20 mA, 2-wire

Lower current limit

Min. 3.6 mA

Upper current limit

Max. 23 mA

Output protected against

Reversed polarity, overvoltage and short-circuiting

Max. load

(UH – 12 V) / 0.023 A

Characteristic

Temperature-linear

Measuring accuracy

 

Error in measurement at 23 °C ± 5 K (73.4 ± 9 °F)

< ± (0.45 K + 0.2 % of full-scale value in K + 1 digit in K)
(< ± (0.81 °F + 0.2 % of full-scale valuein °F + 1 digit in F)

Measuring cycle time

≤ 100 ms

Temperature effect

< ± 0.15 %/10 K (< ± 0.15 %/18 °F)

Power supply effect

< ±0,01 % of full-scale value/V

Vibration influence

< ±0.05 %/g to 500 Hz in all directions (to IEC 68‑2‑64)

Rated operating conditions

 

Ambient conditions

 

Ambient temperature

-25 ... +85 °C (-13 ... +185 °F)

Temperature range for best readability

-10 ... +70 °C (14 ... 158 °F)

Storage temperature

-40 ... +85 °C (-40 ... +185 °F)

Degree of protection

IP65 to EN 60529

Electromagnetic compatibility

EN 61326/A2 Appendix A (2001)

Displays and controls

 

Display

LCD, max. 5 digits, digit height 9 mm (0.354 inch)

Resolution at max. measuring range

0.01 °C (0.01 °F)

Decimal point

Freely parameterizable

Limit values

Freely parameterizable

Limit violation display

Red LED and message on LCD 
(↑ symbol /↓ symbol in case of limit violation in upward / downward direction)

Parameterization

With 3 keys

Units

mA or % or Ω or physical variable: °C, °F, °R, K

Damping

Between 0.1 and 100 s

(increment: 0.1 s) freely parameterizable

Design

 

Weight

≈ 0.7 kg (≈ 1.54 lb)

Non-wetted parts materials

 
  • Field housing

Diam. 80 mm (diam. 3.15 inch), stainless steel, mat. No. 1.4016

  • Cover

Stainless steel, mat. No. 1.4016 with glass

Wetted parts materials

 
  • Protective tube

To DIN 43772 form 8 (March 2000), Ø 14 x 1.5 mm (Ø 0.55 x 0.06 inch)

  • Material

Stainless steel (mat. No. 1.4571/316Ti)

  • Protective tube screw socket

G½B to DIN 3852-2 form A or ½“-14 NPT

  • Material

Stainless steel (mat. No. 1.4571/316Ti)

Measuring insert

Length to fit the ordered protective tube, stainless steel

Connection of display to the protective tube

Radial (type A), can be swiveled by max. ±120° (α)

 

axial (type B), can be swiveled by max. ±360°

Length of the protective tube(U1)

See Ordering data

Electrical connection

Using 2-pole plug connector made of plastic with M16x1.5‑cable entry to EN 175301‑803A, ½"-14 NPT

Power supply

 

Terminal voltage on temperature transmitter (UH)

12 ... 30 V DC

Operating limits

 

Pressure

Max. 40 bar (580 psi)

 


http://anphatautomation.com/SITRANS TW, four-wire system, universal, HART
SITRANS TW, four-wire system, universal, HART


Mã sản phẩm: 7NG3242
Tên sản phẩm: SITRANS TW, four-wire system, universal, HART




Input

 

Selectable filters to suppress the line frequency

50 Hz, 60 Hz, also 10 Hz for special applications (line frequency filter is similar with measuring frequency)

Resistance thermometer

 

Measured variable

Temperature

Measured range

Parameterizable

Measured span

Min. 25 °C (45 °F) x 1/scaling factor

Sensor type

 
  • DIN IEC 751

Pt100 (DIN IEC 751)

  • Acc. to JIS C 1604-81

Pt100 (JIS C1604-81)

  • Acc. to DIN 43760

Ni100 (DIN 43760)

  • Special type (RRTD ≤ 500 Ω)

Multiples or parts of the defined characteristic values can be parameterized (e.g. Pt500, Ni120)

Voltage measurement

Temperature-linear, resistance-linear or customer-specific

Type of connection

  • Normal connection
  • Sum or parallel connection
  • Mean-value or differential connection

Connection

2, 3 or 4-wire circuit

Measuring range limits

Depending on type of connected thermometer (defined range of resistance thermometer)

Sensor breakage monitoring

Monitoring of all connections for open-circuit (function can be switched off)

Sensor short-circuit monitoring

Parameterizable response threshold (function can be switched off)

Resistance-based sensors, potentiometers

 

Measured variable

Ohmic impedance

Measured range

Parameterizable

Measured span

Min. 10 Ω

Voltage measurement

Resistance-linear or customer-specific

Type of connection

  • Normal connection
  • Differential connection
  • Mean-value connection

Connection

2, 3 or 4-wire circuit

Input range

0 ... 6000 Ω;

with mean-value and difference circuits: 0 ... 3000 Ω

Sensor breakage monitoring

Monitoring of all connections for open-circuit (function can be switched off)

Sensor short-circuit monitoring

Parameterizable response threshold (function can be switched off)

Thermocouple elements

 

Measured variable

Temperature

Measured range

Parameterizable

Measured span

Min. 50 °C (32.22 °C) x 1/scaling factor

Measuring range limits

Depend. on type of thermocouple element

Thermocouple

Type B: Pt30 %Rh/Pt6 %Rh (DIN IEC 584)

 

Type C W5 %-Re (ASTM 988)

 

Type D W3 %-Re (ASTM 988)

 

Type E: NiCr/CuNi (DIN IEC 584)

 

Type J: Fe/CuNi (DIN IEC 584)

 

Type K: NiCr/Ni (DIN IEC 584)

 

Type L Fe-CuNi (DIN 43710)

 

Type N: NiCrSi-NiSi (DIN IEC 584)

 

Type R: Pt13 %Rh/Pt (DIN IEC 584)

 

Type S: Pt10 %Rh/Pt (DIN IEC 584)

 

Type T: Cu/CuNi (DIN IEC 584)

 

Type U: Cu/CuNi (DIN 43710)

 

Special type (-10 mV ≤ UTC ≤ 100 mV)

Voltage measurement

Temperature-linear, voltage-linear or customer-specific

Type of connection

  • Normal connection
  • Sum connection
  • Mean-value connection
  • Differential connection

Cold junction compensation

None, internal measurement, external measurement or predefined fixed value

Sensor breakage monitoring

Function can be switched off

mV sensors

 

Measured variable

DC voltage

Measured range

Parameterizable

Measured span

Min. 4 mV

Input range

-120 ... +1000mV

Voltage measurement

Voltage-linear or customer-specific

Overload capacity of inputs

Max. ± 3.5 V

Input resistance

≥ 1 Ω

Sensor current

Approx. 180 μA

Sensor breakage monitoring

Function can be switched off

V sources

 

Measured variable

DC voltage

Measured range

Parameterizable

Voltage measurement

Voltage-linear or customer-specific

Input range/min. span

 
  • Devices with 7NG3242-xxxx1or 7NG3242-xxxx 0 with U/I plug

-1.2 V ... +10 V 0.04 V

  • Devices with 7NG3242-xxxx2

-12 V ... +100 V 0.4 V

  • Devices with 7NG3242-xxxx3

-120 V ... +140 V 4.0 V

Sensor breakage monitoring

Not possible

μA, mA sources

 

Measured variable

DC voltage

Measured range

Parameterizable

Voltage measurement

Current-linear or customer- specific

Input range/min. span

 
  • Devices with 7NG3242-xxxx4

-12 μA ... +100 μA/0.4 μA

  • Devices with 7NG3242-xxxx5

-120 μA ... +1000 μA/4 μA

  • Devices with 7NG3242-xxxx6

-1.2 mA ... +10 mA 0.04 mA

  • Devices with 7NG3242-xxxx7or 7NG3242-xxxx 0 with U/I plug

-12 mA ... +100 mA 0.4 mA

  • Devices with 7NG3242-xxxx8

-120 mA ... +1000 mA 4 mA

Sensor breakage monitoring

Not possible

Output

 

Output signal

Load-independent direct current 0/4 ... 20 mA, can be switched to load-independent DC voltage 0/2 ... 10 V using plug-in jumpers.

Current 0/4 ... 20 mA

 
  • Overrange

-0.5 ... +23.0 mA, continuously adjustable

  • Output range following sensor fault

-0.5 ... +23.0 mA, continuously adjustable

  • Load

≤ 650 Ω

  • Open-circuit voltage

≤ 30 V

Voltage 0/2 ... 10 V

 
  • Overrange

-0.25 ... +10.75 V, continuously adjustable

  • Output range following sensor fault

-0.25 ... +10.75 V, continuously adjustable

  • Load resistance

≥ 1 kΩ

  • Load capacitance

≤ 10 nF

  • Short-circuit voltage

≤ 100 mA (not permanently short-circuit-proof)

  • Electrical damping
 
  • Adjustable time constant T63

0 ... 100 s, in steps of 0.1 s

  • Current source/voltage source

Continuously adjustable within the total operating range

Sensor fault/limit signalling

By operation indicator, relay output or HART interface

Operation indicator

Flashing signal

  • Limit violation

Flashing frequency 5 Hz

  • Overrange

Flashing frequency 1 Hz

Relay output

Either as NO or NC contact with 1 changeover contact

  • Switching capacity

≤ 150 W, ≤ 625 VA

  • Switching voltage

≤ 125 V DC, ≤ 250 V AC

  • Switching current

≤ DC 2.5 A

Overrange

Signalling of sensor or line breakage and sensor short-circuit

Limit monitoring

 
  • Operating delay

0 ... 10 s

  • Monitoring functions of limit module
  • Sensor fault (breakage and/or short-circuit)
  • Lower and upper limit
  • Window (combination of lower and upper limits)
  • Limit and sensor fault detection can be combined
  • Hysteresis

Parameterizable between 0 and 100 % of measuring range

Power supply

 

Universal power supply unit

115/230 V AC/DC or 24 V AC/DC

Tolerance range for power supply

 
  • With 115/230 V AC/DC PSU

80 ... 300 V DC; 90 ... 250 V AC

  • With 24 V AC/DC PSU

18 ... 80 V DC; 20.4 ... 55.2 V AC (in each case interruption-resistant up to 20 ms in the complete tolerance range)

Tolerance range for mains frequency

47 ... 63 Hz

Power consumption with

 
  • 230 V AC

≤ 5 VA

  • 230 V DC

≤ 5 W

  • 24 V AC

≤ 5 VA

  • 24 V DC

≤ 5 W

Electrical isolation

 

Electrically isolated circuits

Input, output, power supply and sensor fault/limit monitoring output are electrically isolated from one another. The HART interface is electrically connected to the output.

Working voltage between all electrically isolated circuits

The voltage U eff between any two terminals must not exceed 300 V

Measuring accuracy

 

Measurement error

 
  • Error in the internal cold junction

≤ 3 °C ± 0,1 °C/10 °C (≤ 5.4 °F ± 0,18  °F/18 °F)

  • Error of external cold junction terminal 7NG3092-8AV

≤ 0.5 °C ± 0,1 °C/10 °C (≤ 0.9 °F ± 0.18 °F/18 °F)

  • Digital output

See "Digital error"

  • Analog output IAN or UAN

≤ 0.05 % of span in addition to digital error

Influencing effects (referred to the digital output)

Compared to the max. span:

  • Temperature drift

≤ 0.08 %/10 °C (≤ 0.08 %/18 °F)

≤ 0.2 % in the range -10 ... +60 °C (14 ... 140 °F)

  • Long-term drift

≤ 0.1 %/year

Influencing effects referred to the analog output IAN or UAN

Compared to the span:

  • Temperature drift

≤ 0.08 %/10°C (≤ 0.08 %/18 °F)

≤ 0.2 % in the range -10 ... +60 °C (14 ... 140 °F)

  • Power supply

≤ 0.05 %/10 V

  • Load with current output

≤ 0.05 % with change from 50 ... 650 Ω

  • Load with voltage output

≤ 0.1 % with change in load current from 0 … 10 mA

  • Long-term drift (start-of-scale value, span)

≤ 0.03 %/month

Response time (T63without electrical damping)

≤ 0.2 s

Electromagnetic compatibility

According to EN 61 326 and NAMUR NE21

Certificate and approvals

 

ATEX

To DIN EN 50014: 1997, EN 50020: 1994

Intrinsic safety to EN 50 020

 
  • for 7NG3242-xAxxx

II (1) G D [EEx ia/ib ] IIB

  • for 7NG3242-xBxxx

II (1) G D [EEx ia/ib ] IIC

EC-Type Examination Certificate

TÜV (German Technical Inspectorate) 01 ATEX 1675

Rated conditions

 

Installation conditions

 

Location (for devices with explosion protection)

 
  • Transmitters

Outside the potentially explosive atmosphere

  • Sensor

Within the potentially explosive atmosphere zone 1 (also in zone 0 in conjunction with the prescribed protection requirements for the sensor)

Ambient conditions

 

Permissible ambient temperature

-25 ... +70 °C (-13 ... +158 °F)

Permissible storage temperature

-40 ... +85 °C (-40 ... +185 °F)

Climatic class

 
  • Relative humidity

5 ... 95 %, no condensation

Design

 

Weight

Approx. 0.24 kg (0.53 lb)

Enclosure material

PBT, glass-fibre reinforced

Degree of protection to IEC 529

IP20

Degree of protection to VDE 0100

Protection class I

Type of installation

35-mm top hat rail (1.38 inch) (DIN EN 50022) or 32-mm G-type rail (1.26 inch) (DIN EN 50035)

Electrical connection / process connection

Screw plug connectors, max. 2.5 mm² (0.01 inch²)

Parameterization interface

 

Protocol

HART, version 5.9

Load with connection of

 
  • HART communicator

230 ... 650 Ω

  • HART modem

230 ... 500 Ω

Software for PC/laptop

SIMATIC PDM version V5.1 and later


Digital error

Resistance thermometer

Input

Measured range

Max. permissible line resistance

Digital error

 

°C (°F)

Ω

°C (°F)

DIN IEC 751

   
  • Pt10

-200 ... +850 (‑328 ... +1562)

20

3.0 (5.4)

  • Pt50

-200 ... +850 (‑328 ... +1562)

50

0.6 (1.1)

  • Pt100

-200 ... +850 (‑328 ... +1562)

100

0.3 (0.5)

  • Pt200

-200 ... +850 (‑328 ... +1562)

100

0.6 (1.1)

  • Pt500

-200 ... +850 (‑328 ... +1562)

100

1.0 (1.8)

  • Pt1000

-200 ... +850 (‑328 ... +1562)

100

1.0 (1.8)

JIS C 1604-81

   
  • Pt10

-200 ... +649 (‑328 ... +1200)

20

3.0 (5.4)

  • Pt50

-200 ... +649 (‑328 ... +1200)

50

0.6 (1.1)

  • Pt100

-200 ... +649 (‑328 ... +1200)

100

0.3 (0.5)

DIN 43760

   
  • Ni50

-60 ... +250 (‑76 ... +482)

50

0.3 (0.5)

  • Ni100

-60 ... +250 (‑76 ... +482)

100

0.3 (0.5)

  • Ni120

-60 ... +250 (‑76 ... +482)

100

0.3 (0.5)

  • Ni1000

-60 ... +250 (‑76 ... +482)

100

0.3 (0.5)


Resistance-based sensors

Input

Measured range

Max. permissible line resistance

Digital error

 

Ω

Ω

Ω

Resistance (linear)

0 ... 24

5

0.08

 

0 ... 47

15

0.06

 

0 ... 94

30

0.06

 

0 ... 188

50

0.08

 

0 ... 375

100

0.1

 

0 ... 750

100

0.2

 

0 ... 1500

75

1.0

 

0 ... 3000

100

1.0

 

0 ... 6000

100

2.0


Thermocouple elements

Input

Measured range

Digital error 1)

 

°C (°F)

°C (°F)

Type B

0 ... +1820 (+32 ... +3308)

3 (5.4)

Type C

0 ... +2300 (+32 ... +4172)

2 (3.6)

Type D

0 ... +2300 (+32 ... +4172)

1 (1.8)

Type E

-200 ... +1000 (‑328 ... +1832)

1 (1.8)

Type J

-210 ... +1200 (‑346 ... +2192)

1 (1.8)

Type K

-200 ... +1372 (‑328 ... +2501)

1 (1.8)

Type L

-200 ... +900 (‑328 ... +1652)

2 (3.6)

Type N

-200 ... +1300 (‑328 ... +2372)

1 (1.8)

Type R

-50 ... +1760 (‑58 ... +3200)

2 (3.6)

Type S

-50 ... +1760 (‑58 ... +3200)

2 (3.6)

Type T

-200 ... +400 (‑328 ... +752)

1 (1.8)

Type U

-200 ... +600 (‑328 ... +1112)

2 (3.6)


1) Accuracy data refer to the largest error in the complete measuring range

Voltage/current sources

Input

Measuring range mV

Digital error μV

mV sources (linear)

-1  ... +16

35

 

-3 ... +32

20

 

-7 ... +65

20

 

-15 ... +131

50

 

-31 ... +262

100

 

-63 ... +525

200

 

-120 ... +1000

300

 

Measuring range V

Digital error mV

V sources (linear)

-1,2 ... +10

3

 

-12 ... +100

30

 

-120 ... +140

300

 

Measuring range μA/mA

Digital error μA

μA/mA sources (linear)

-12 ... 100 Î¼A

0,05

 

-120 ... +1000 Î¼A

0,5

 

-1,2 ... +10 mA

5

 

-12 ... +100 mA

50

 

-120 ... +1000 mA

500

 


http://anphatautomation.com/SITRANS TH100, two-wire system (Pt100)
SITRANS TH100, two-wire system (Pt100)


Mã sản phẩm: 7NG3211-0NN00
Tên sản phẩm: SITRANS TH100, two-wire system (Pt100)





SITRANS TH100

 

Input

 

Resistance thermometer

 

Measured variable

Temperature

Sensor type

PT100 to IEC 60751

Characteristic curve

Temperature-linear

Type of connection

2-, 3- or 4-wire circuit

Resolution

14 bit

Measuring accuracy

 
  • Span <250 °C (450 °F)

< 0.25 °C (0.45 °F)

  • Span >250 °C (450 °F)

< 0.1 % of span

Repeatability

< 0.1 °C (0.18 °F)

Measuring current

approx. 0.4 mA

Measuring cycle

< 0.7 s

Measuring range

-200 ... +850 °C (-328 ... +1562 °F)

Measuring span

25 ... 1050 °C (77 ... 1922 °F)

Unit

°C or °F

Offset

programmable:
-100 ... +100 °C (-180 ... +180 °F)

Line resistance

Max. 20 Ω (total from feeder and return conductor)

Noise rejection

50 and 60 Hz

Output

 

Output signal

4 ... 20 mA, two-wire

Auxiliary power supply

8.5 ... 36 V DC (30 V for Ex)

Max. load

(Uaux – 8.5 V)/0.023 A

Overrange

3.6 ... 23 mA, infinitely adjustable (default value: 3.84 ... 20.5 mA)

Error signal (in the event of sensor breakage)

3.6 ... 23 mA, infinitely adjustable (default value: 3.6 mA or 22.8 mA)

Damping time

0 ... 30 s

Protection

Against reversed polarity

Resolution

12 bit

Accuracy at 23 °C (73.4 °F)

< 0.1 % of span

Temperature effect

< 0.1 %/10 °C (0.1 %/18 °F)

Effect of auxiliary power

< 0.01 % of span/V

Effect of load impedance

< 0.025 % of max. span/100 Ω

Long-term drift

 
  • in the first month

< 0.025 % of max. span

  • after one year

< 0.035 % of max. span

  • after 5 years

< 0.05 % of max. span

Ambient conditions

 

Ambient temperature range

-40 ... +85 °C (-40 ... +185 °F)

Storage temperature range

-40 ... +85 °C (-40 ... +185 °F)

Relative humidity

98 %, with condensation

Electromagnetic compatibility

According to EN 61326 and NAMUR NE21

Construction

 

Weight

50 g

Dimensions

See dimensional drawing

Material

Molded plastic

Cross-section of cables

Max. 2.5 mm2 (AWG 13)

Degree of protection to IEC 60529

 
  • Enclosure

IP40

  • Terminals

IP00

Certificates and approvals

 

Explosion protection ATEX

 

EC type test certificate

PTB 05 ATEX 2049X

  • "Intrinsic safety" type of protection

II 1G EEx ia IIC T6/T4
II 2(1)G EEx ib/ia IIC T6/T4

  • "Operating equipment that is non-ignitable and has limited energy" type of protection

II 3G EEx nAL IIC T6/T4

Explosion protection: FM for USA

 
  • FM approval

PID 3024169

  • Degree of protection

IS/Cl I, II, III/Div 1/GP ABCDEFG T4, T5, T6
IS/Cl I/ZN 0, 1/AEx ia IIC T4, T5, T6
Nl/Cl I, II, III/Div 2/GP ABCDFG T4, T5, T6
Cl I/ZN 2/GP IIC T4, T5, T6

Explosion protection to FM for Canada (cFMUS)

 
  • FM approval

PID 3024169

  • Degree of protection

IS/Cl I, II, III/Div 1/GP ABCDEFG T4, T5, T6
IS/Cl I/ZN 0, 1/AEx ia IIC T4, T5, T6
Nl/Cl I, II, III/Div 2/GP ABCDFG T4, T5, T6
Cl I/ZN 2/GP IIC T4, T5, T6

  

Software requirements for SIPROM T

 

PC operating system

Windows ME, 2000 and XP; also Windows 95, 98 and 98SE, but only in connection with RS 232 modem.

Factory setting:

 
  • Pt100 (IEC 751) with 3-wire circuit
  • Measuring range: 0 ... 100 °C (32 ... 212 °F)
  • Error signal in the event of sensor breakage: 22.8 mA
  • Sensor offset: 0 °C (0 °F)

Damping 0.0 s

 


Overview:

Features:

Video clips:

Screen shots:

Links: