Resistance thermometer
|
|
Mã sản phẩm:
7MC...
Tên sản phẩm:
Resistance thermometer
Selection of suitable materials for protective tube and neck tubeDo you have high temperatures, high pressures, aggressive media? Or are you temperature measurements taken in fast flowing media? We can help you and have the right solution. You even have a choice of mounting types. Whether flange, screwed gland or welded connection - for us it's no problem. Following resistance thermometers are available: - Flue gas resistance thermometer
- Low-pressure screw-in resistance thermometer
- Without neck tube
- With neck tube
- High-pressure screw-in resistance thermometer
- High-pressure screw-in resistance thermometer
- Flange-type resistance thermometer
- Resistance thermometer for damp rooms
The following temperature transmitters are available for installation in the connection head - SITRANS TH100
- SITRANS TH200/TH300
- SITRANS TH400
|
|
|
|
|
SITRANS TR200
|
|
Mã sản phẩm:
7NG3032-0JN00
Tên sản phẩm:
SITRANS TR200
Input | | Resistance thermometer | | Measured variable | Temperature | Sensor type | | | Pt25 … Pt1000 | - To JIS C 1604; a=0.00392 K-1
| Pt25 … Pt1000 | | Ni25 … Ni1000 | | over special characteristic (max. 30 points) | Sensor factor | 0.25 ... 10 (adaptation of the basic type, e.g. Pt100 to version Pt25 ... Pt1000) | Units | °C or °F | Connection | | | 1 resistance thermometer (RTD) in 2-wire, 3-wire or 4-wire system | - Generation of average value
| 2 identical resistance thermometers in 2-wire system for generation of average temperature | | 2 identical resistance thermometers (RTD) in 2-wire system (RTD 1 – RTD 2 or RTD 2 – RTD 1) | Interface | | | Parameterizable line resistance ≤ 100 Ω (loop resistance) | | No balancing required | | No balancing required | Sensor current | ≤ 0.45 mA | Response time T63 | ≤ 250 ms for 1 sensor with open-circuit monitoring | Open-circuit monitoring | Always active (cannot be disabled) | Short-circuit monitoring | can be switched off (value is adjustable) | Measuring range | Parameterizable (see table "Digital measuring errors") | Min. measured span | 10 °C (18 °F) | Characteristic curve | Temperature-linear or special characteristic | Resistance-based sensors | | Measured variable | Actual resistance | Sensor type | Resistance-based, potentiometers | Units | Ω | Connection | | | 1 resistance-based sensor (R) in 2-wire, 3-wire or 4-wire system | - Generation of average value
| 2 resistance-based sensors in 2-wire system for generation of average value | | 2 resistance thermometers in 2-wire system (R1 – R2 or R2 – R1) | Interface | | | Parameterizable line resistance ≤ 100 Ω (loop resistance) | | No balancing required | | No balancing required | Sensor current | ≤ 0.45 mA | Response time T63 | ≤ 250 ms for 1 sensor with open-circuit monitoring | Open-circuit monitoring | Always active (cannot be disabled) | Short-circuit monitoring | can be switched off (value is adjustable) | Measuring range | Parameterizable, max. 0 ... 2200 Ω (see Table "Digital measuring errors") | Min. measured span | 5 Ω ... 25 Ω (see Table "Digital measuring errors") | Characteristic curve | Resistance-linear or special characteristic | Thermocouples | | Measured variable | Temperature | Sensor type (thermocouples) | | | Pt30Rh-Pt6Rh to DIN IEC 584 | | W5 %-Re acc. to ASTM 988 | | W3 %-Re acc. to ASTM 988 | | NiCr-CuNi to DIN IEC 584 | | Fe-CuNi to DIN IEC 584 | | NiCr-Ni to DIN IEC 584 | | Fe-CuNi to DIN 43710 | | NiCrSi-NiSi to DIN IEC 584 | | Pt13Rh-Pt to DIN IEC 584 | | Pt10Rh-Pt to DIN IEC 584 | | Cu-CuNi to DIN IEC 584 | | Cu-CuNi to DIN 43710 | Units | °C or °F | Connection | | | 1 thermocouple (TC) | - Generation of average value
| 2 identical thermocouples (TC) | | 2 identical thermocouples (TC) TC1 – TC2 or TC2 – TC1 | Response time T63 | ≤ 250 ms for 1 sensor with open-circuit monitoring | Open-circuit monitoring | can be switched off | Cold junction compensation | | | With integrated Pt100 resistance thermometer | | With external Pt100 IEC 60571 (2-wire or 3-wire connection) | | Cold junction temperature can be set as fixed value | Measuring range | Parameterizable (see table "Digital measuring errors") | Min. measured span | Min. 50 ... 100 °C (90 ... 180 °F) (see table "Digital measuring errors") | Characteristic curve | Temperature-linear or special characteristic | mV sensor | | Measured variable | DC voltage | Sensor type | DC voltage source (DC voltage source possible over an externally connected resistor) | Units | mV | Response time T63 | ≤ 250 ms for 1 sensor with open-circuit monitoring | Open-circuit monitoring | can be switched off | Measuring range | Parameterizable max. -100 … 1100 mV |
|
|
|
|
|
SITRANS TR300
|
|
Mã sản phẩm:
7NG3033-0JN00
Tên sản phẩm:
SITRANS TR300
Input | | Resistance thermometer | | Measured variable | Temperature | Sensor type | | | Pt25 to Pt1000 | - to JIS C 1604; a=0.00392 K-1
| Pt25 to Pt1000 | | Ni25 to Ni1000 | | Over special characteristic (max. 30 points) | Sensor factor | 0.25 ... 10 (adaptation of the basic type, e.g. Pt100 to version Pt25 ... Pt1000) | Units | °C or °F | Connection | | | 1 resistance thermometer (RTD) in 2-wire, 3-wire or 4-wire system | - Generation of average value
| 2 identical resistance thermometers in 2-wire system for generation of average temperature | | 2 identical resistance thermometers (RTD) in 2-wire system (RTD 1 – RTD 2 or RTD 2 – RTD 1) | Interface | | | Parameterizable line resistance ≤ 100 Ω (loop resistance) | | No balancing required | | No balancing required | Sensor current | ≤ 0.45 mA | Response time T63 | ≤ 250 ms for 1 sensor with open-circuit monitoring | Open-circuit monitoring | Always active (Cannot switched off) | Short-circuit monitoring | Can be switched off (value is adjustable) | Range | Parameterizable (see table "Digital measuring errors") | Min. measured span | 10 °C (18 °F) | Characteristic | Temperature-linear or special characteristic | Resistance-based sensors | | Measured variable | Actual resistance | Sensor type | Resistance-based, potentiometers | Units | Ω | Connection | | | 1 resistance-based sensor (R) in 2-wire, 3-wire or 4-wire system | - Generation of average value
| 2 resistance-based sensors in 2-wire system for generation of average value | | 2 resistance thermometers in 2-wire system (R1 – R2 or R2 – R1) | Interface | | | Parameterizable line resistance ≤ 100 Ω (loop resistance) | | No balancing required | | No balancing required | Sensor current | ≤ 0.45 mA | Response time T63 | ≤ 250 ms for 1 sensor with open-circuit monitoring | Open-circuit monitoring | Always active (cannot switched off) | Short-circuit monitoring | Can be switched off (value is adjustable) | Range | Parameterizable, max. 0 ... 2200 Ω (see Table "Digital measuring errors") | Min. measured span | 5 Ω ... 25 Ω (see Table "Digital measuring errors") | Characteristic | Resistance-linear or special characteristic | Thermocouple elements | | Measured variable | Temperature | Sensor type (thermocouples) | | | Pt30Rh-Pt6Rh to DIN IEC 584 | | W5 %-Re to ASTM 988 | | W3 %-Re to ASTM 988 | | NiCr-CuNi to DIN IEC 584 | | Fe-CuNi to DIN IEC 584 | | NiCr-Ni to DIN IEC 584 | | Fe-CuNi to DIN 43710 | | NiCrSi-NiSi to DIN IEC 584 | | Pt13Rh-Pt to DIN IEC 584 | | Pt10Rh-Pt to DIN IEC 584 | | Cu-CuNi to DIN IEC 584 | | Cu-CuNi to DIN 43710 | Units | °C or °F | Connection | | | 1 thermocouple (TC) | - Generation of average value
| 2 thermocouples (TC) | | 2 thermocouples (TC) TC1 – TC2 or TC2 – TC1 | Response time T63 | ≤ 250 ms for 1 sensor with open-circuit monitoring | Open-circuit monitoring | Can be switched off | Cold junction compensation | | | With integrated Pt100 resistance thermometer | | With external Pt100 IEC 60571 (2-wire or 3-wire connection) | | Cold junction temperature can be set as fixed value | Range | Parameterizable (see table "Digital measuring errors") | Min. measured span | Min. 50 ... 199 °C (90 ... 180 °F) (see table "Digital measuring errors") | Characteristic | Temperature-linear or special characteristic | mV Sensor | | Measured variable | DC voltage | Sensor type | DC voltage source (DC voltage source possible over an externally connected resistor) | Units | mV | Response time T63 | ≤ 250 ms for 1 sensor with open-circuit monitoring | Open-circuit monitoring | Can be switched off | Short-circuit monitoring | Can be switched off (value is adjustable) | Range | Parameterizable max. -100 … 1100 mV | Min. measured span | 2 mV or 20 mV | Overload capacity of the input | -1.5 ... +3.5 V DC | Input resistance | ≥ 1 MΩ | Characteristic | Voltage-linear or special characteristic | Output | | Output signal | 4 ... 20 mA, 2-wire Communication acc. to HART Rev. 5.9 | Power supply | 11 ... 35 V DC (to 30 V with EEx) | Max. load | (Uaux – 11 V)/0.023 A | Overrange | 3.6 ... 23 mA, continuously adjustable (default range: 3.84 ... 20.5 mA) | Error signal (e.g. in the event of sensor breakage) | 3.6 ... 23 mA, continuously adjustable (default value: 22.8 mA) | Sample cycle | 0.25 s nominal | Damping | Software filter 1st order 0 ... 30 s (parameterizable) | Protection | Against reversed polarity | Electrically isolated | Input against output (1 kVeff) | Measuring accuracy | | Digital measuring errors | See Table "Digital measuring errors" | Reference conditions | | | 24 V ± 1 % | | 500 Ω | | 23 °C | | > 5 min | Error in the analog ouput (digital/analog converter) | < 0.1 % of span | Error due to internal cold junction | < 0.55 °C (0.9 °F) | Temperature effect | < 0.1 % der max. span/10°C (18 °F) | Power supply effect | < 0.005 % of span/V | Effect of load impedance | < 0.012 % of span/100 Ω | Long-term drift | | | < 0.02 % of max. span | | < 0.03 % of max. span | | < 0.04 % of max. span | Rated conditions | | Ambient temperature | | Storage temperature | -40 ... +85 °C (-40 ... 185 °F) | Functional temperature | -40 ... +85 °C (-40 ... 185 °F) | Relative humidity | < 98 %, with condensation | Electromagnetic compatibility | acc. to DIN EN 61326 and NAMUR NE21 | Construction | | Material | Plastic, electronic module potted | Approx. weight | 122 g (0.27 lb) | Dimensions | See "Dimension drawings" | Cross-section of cables | Max. 2.5 mm² (AWG 13) | Degree of protection to EN 60529 | | | IP40 | | IP00 | Certificate and approvals | | Explosion protection ATEX | | EC type test certificate | PTB 07 ATEX 2032X | - "Intrinsic safety" type of protection
| II 2(1) G Ex ia/ib IIC T6/T4 II 3(1) G Ex ia/ic IIC T6/T4 II 2(1) D Ex iaD/ibD 20/21 T115 °C | - Type of protection, "equipment has limited energy"
| II 3 G Ex nL IIC T6/T4 | - Type of protection, "equipment is non-arcing"
| II 3 G Ex nA IIC T6/T4 | Software requirements for SIPROM T | | PC operating system: | Windows ME, 2000 and XP; also Windows 95, 98 and 98 SE, but only in connection with RS 232 modem. |
Factory setting: - Pt100 (IEC 751) with three-wire circuit
- Measuring range: 0 ... 100 °C (32 ... 212 °F)
- Fault current: 22.8 mA
- Sensor offset: 0 °C (0 °F)
- Damping 0.0 s
Digital measuring errorsResistance thermometer input | Range | Min. measured span | Digital accuracy |
---|
| °C (°F) | °C | (°F) | °C | (°F) | to IEC 60751 | | | | | | Pt25 | -200 ... +850 (-328 ... +1562) | 10 | (18) | 0.2 | (0.36) | Pt50 | -200 ... +850 (-328 ... +1562) | 10 | (18) | 0.15 | (0.27) | Pt100 ... Pt200 | -200 ... +850 (-328 ... +1562) | 10 | (18) | 0.1 | (0.18) | Pt500 | -200 ... +850 (-328 ... +1562) | 10 | (18) | 0.15 | (0.27) | Pt1000 | -200 ... +350 (-328 ... +662) | 10 | (18) | 0.15 | (0.27) | to JIS C1604-81 | | | | | | Pt25 | -200 ... +649 (-328 ... +1200) | 10 | (18) | 0.2 | (0.36) | Pt50 | -200 ... +649 (-328 ... +1200) | 10 | (18) | 0.15 | (0.27) | Pt100 ... Pt200 | -200 ... +649 (-328 ... +1200) | 10 | (18) | 0.1 | (0.18) | Pt500 | -200 ... +649 (-328 ... +1200) | 10 | (18) | 0.15 | (0.27) | Pt1000 | -200 ... +350 (-328 ... +662) | 10 | (18) | 0.15 | (0.27) | Ni 25 to Ni1000 | -60 ... +250 (-76 ... +482) | 10 | (18) | 0.1 | (0.18) |
Resistance-based sensors Input | Range | Min. measured span | Digital accuracy |
---|
| Ω | Ω | Ω | Resistance | 0 ... 390 | 5 | 0.05 | Resistance | 0 ... 2200 | 25 | 0.25 |
Thermocouples Input | Measuring range | Min. measured span | Digital accuracy |
---|
| °C | (°F) | °C | (°F) | °C | (°F) | Type B | 0 ... 1820 | (32 ... 3308) | 100 | (180) | 21) | (3.60)1) | Type C (W5) | 0 ... 2300 | (32 ... 4172) | 100 | (180) | 2 | (3.60) | Type D (W3) | 0 ... 2300 | (32 ... 4172) | 100 | (180) | 12) | (1.80)2) | Type E | -200 ... +1000 | (-328 ... +1832) | 50 | (90) | 1 | (1.80) | Type J | -210 ... +1200 | (-346 ... +2192) | 50 | (90) | 1 | (1.80) | Type K | -230 ... +1370 | (-382 ... +2498) | 50 | (90) | 1 | (1.80) | Type L | -200 ... +900 | (-328 ... +1652) | 50 | (90) | 1 | (1.80) | Type N | -200 ... +1300 | (-328 ... +2372) | 50 | (90) | 1 | (1.80) | Type R | -50 ... +1760 | (-58 ... +3200) | 100 | (180) | 2 | (3.60) | Type S | -50 ... +1760 | (-58 ... +3200) | 100 | (180) | 2 | (3.60) | Type T | -200 ... +400 | (-328 ... +752) | 40 | (72) | 1 | (1.80) | Type U | -200 ... +600 | (-328 ... +1112) | 50 | (90) | 2 | (3.60) |
1) The digital accuracy in the range 0 to 300 °C (32 to 572 °F) is 3 °C (5.4 °F). 2) The digital accuracy in the range 1750 to 2300 °C (3182 to 4172 °F) is 2 °C (3.6 °F). mV Sensor input | Range | Min. measured span | Digital accuracy |
---|
| mV | mV | μV | mV Sensor | -10 ... +70 | 2 | 40 | mV Sensor | -100 ... +1100 | 20 | 400 |
The digital accuracy is the accuracy after the analog/digital conversion including linearization and calculation of the measured value. An additional error is generated in the output current 4 to 20 mA as a result of the digital/analog conversion of 0.1 % of the set span (digital-analog error). The total error under reference conditions at the analog output is the sum from the digital error and the digital-analog error (poss. with the addition of cold junction errors in the case of thermocouple measurements).
|
|
|
|
|
SITRANS TH300
|
|
Mã sản phẩm:
7NG3212-0NN00
Tên sản phẩm:
SITRANS TH300
Input | | Resistance thermometer | | Measured variable | Temperature | Sensor type | | | Pt25 … Pt1000 | - To JIS C 1604; a = 0.00392 K-1
| Pt25 … Pt1000 | | Ni25 … Ni1000 | | over special characteristic (max. 30 points) | Sensor factor | 0.25 ... 10 (adaptation of the basic type, e.g. Pt100 to version Pt25 ... Pt1000) | Units | °C or °F | Connection | | | 1 resistance thermometer (RTD) in 2-wire, 3-wire or 4-wire system | - Generation of average value
| 2 identical resistance thermometers in 2-wire system for generation of average temperature | | 2 identical resistance thermometers (RTD) in 2-wire system (RTD 1 – RTD 2 or RTD 2 – RTD 1) | Interface | | | Parameterizable line resistance ≤ 100 Ω (loop resistance) | | No balancing required | | No balancing required | Sensor current | ≤ 0.45 mA | Response time | ≤ 250 ms for 1 sensor with open-circuit monitoring | Open-circuit monitoring | can be switched off | Short-circuit monitoring | can be switched off (value is adjustable) | Measuring range | Parameterizable (see table "Digital measuring errors") | Min. measured span | 10 °C (18 °F) | Characteristic curve | Temperature-linear or special characteristic | Resistance-based sensors | | Measured variable | Actual resistance | Sensor type | Resistance-based, potentiometers | Units | Ω | Connection | | | 1 resistance-based sensor (R) in 2-wire, 3-wire or 4-wire system | - Generation of average value
| 2 resistance-based sensors in 2-wire system for generation of average value | | 2 resistance thermometers in 2-wire system (R1 – R2 or R2 – R1) | Interface | | | Parameterizable line resistance ≤ 100 Ω (loop resistance) | | No balancing required | | No balancing required | Sensor current | ≤ 0.45 mA | Response time | ≤ 250 ms for 1 sensor with open-circuit monitoring | Open-circuit monitoring | can be switched off | Short-circuit monitoring | can be switched off (value is adjustable) | Measuring range | Parameterizable, max. 0 ... 2200 Ω (see Table "Digital measuring errors") | Min. measured span | 5 Ω ... 25 Ω (see Table "Digital measuring errors") | Characteristic curve | Resistance-linear or special characteristic | Thermocouples | | Measured variable | Temperature | Sensor type (thermocouples) | | | Pt30Rh-Pt6Rh to DIN IEC 584 | | W5 %-Re acc. to ASTM 988 | | W3 %-Re acc. to ASTM 988 | | NiCr-CuNi to DIN IEC 584 | | Fe-CuNi to DIN IEC 584 | | NiCr-Ni to DIN IEC 584 | | Fe-CuNi to DIN 43710 | | NiCrSi-NiSi to DIN IEC 584 | | Pt13Rh-Pt to DIN IEC 584 | | Pt10Rh-Pt to DIN IEC 584 | | Cu-CuNi to DIN IEC 584 | | Cu-CuNi to DIN 43710 | Units | °C or °F | Connection | | | 1 thermocouple (TC) | - Generation of average value
| 2 thermocouples (TC) | | 2 thermocouples (TC) TC1 – TC2 or TC2 – TC1) | Response time | ≤ 250 ms for 1 sensor with open-circuit monitoring | Open-circuit monitoring | can be switched off | Cold junction compensation | | | With integrated Pt100 resistance thermometer | | With external Pt100 IEC 60571 (2-wire or 3-wire connection) | | Cold junction temperature can be set as fixed value | Measuring range | Parameterizable (see table "Digital measuring errors") | Min. measured span | Min. 50 ... 199 °C (90 ... 180 °F) (see table "Digital measuring errors") | Characteristic curve | Temperature-linear or special characteristic | mV sensor | | Measured variable | DC voltage | Sensor type | DC voltage source (DC voltage source possible over an externally connected resistor) | Units | mV | Response time | ≤ 250 ms for 1 sensor with open-circuit monitoring | Open-circuit monitoring | can be switched off | Short-circuit monitoring | can be switched off (value is adjustable) | Measuring range | -10 ... +70 mV -100 … +1100 mV | Min. measured span | 2 mV or 20 mV | Overload capability of the input | -1.5 ... +3.5 V DC | Input resistance | ≥ 1 MΩ | Characteristic curve | Voltage-linear or special characteristic | Output | | Output signal | 4 ... 20 mA, 2-wire with communication acc. to HART Rev. 5.9 | Auxiliary power supply | 11 ... 35 V DC (to 30 V with EEx) | Max. load | (Uaux – 11 V)/0.023 A | Overrange | 3.6 ... 23 mA, infinitely adjustable (default range: 3.80 mA ... 20.50 mA) | Error signal (e.g. in the event of sensor breakage) | 3.6 ... 23 mA, infinitely adjustable (default value: 22.8 mA) | Sample cycle | 0.25 s nominal | Damping | Software filter 1st order 0 ... 30 s (parameterizable) | Protection | Against reversed polarity | Electrically isolated | Input against output (1 kVeff) | Measuring accuracy | | Digital measuring errors | See Table "Digital measuring errors" | Reference conditions | | | 24 V ± 1 % | | 500 Ω | | 23 °C | | > 5 min | Error in the analog output (digital/analog converter) | < 0.1 % of span | Error due to internal cold junction | < 0.5 °C (0.9 °F) | Temperature effect | < 0.1 % of max. span/10 °C (18 °F) | Auxiliary power supply effect | < 0.005 % of span/V | Effect of load impedance | < 0.012 % of span/100 Ω | Long-term drift | | | < 0.02 % of max. span | | < 0.03 % of max. span | | < 0.04 % of max. span | Conditions of use | | Ambient conditions | | Ambient temperature range | -40 ... +85 °C (-40 ... 185 °F) | Storage temperature range | -40 ... +85 °C (-40 ... 185 °F) | Relative humidity | < 98 %, with condensation | Electromagnetic compatibility | acc. to EN 61326 and NE21 | Construction | | Material | Molded plastic | Weight | 50 g (0.11 lb) | Dimensions | See "Dimensional drawings" | Cross-section of cables | Max. 2.5 mm² (AWG 13) | Degree of protection to IEC 60529 | | | IP40 | | IP00 | Certificates and approvals | | Explosion protection ATEX | | EC type test certificate | PTB 05 ATEX 2040X | - "Intrinsic safety" type of protection
| II 1 G Ex ia IIC T6/T4 II 2(1) G Ex ib/ia IIC T6/T4 | - "Operating equipment that is non-ignitable and has limited energy" type of protection
| II 3 G Ex nL IIC T6/T4 II 3 G Ex nA IIC T6/T4 | Explosion protection: FM for USA | | | FM 3024169 | | IS/Cl I, II, III/Div 1/GP ABCDEFG T6, T5, T4 IS/Cl I/ZN 0/AEx ia IIC T6, T5, T4 NI/Cl I, II, III/Div 2/GP ABCDFG T6, T5, T4 NI/Cl I/ZN 2/IIC T6, T5, T4 | Explosion protection to FM for Canada (cFMUS) | | | FM 3024169C | | IS/Cl I/ZN 0/Ex ia IIC T6, T5, T4 NI/Cl I/ZN 2/Ex nAL IIC T6, T5, T4 |
Factory setting: - Pt100 (IEC 751) with 3-wire circuit
- Measuring range: 0 ... 100 °C (32 ... 212 °F)
- Fault current: 22.8 mA
- Sensor offset: 0 °C (0 °F)
- Damping 0.0 s
Digital measuring errorsResistance thermometer Input | Measuring range | Min. measured span | Digital accuracy |
---|
| °C (°F) | °C | (°F) | °C | (°F) | to IEC 60751 | | | | | | Pt25 | -200 ... +850 (-328 ... +1562) | 10 | (18) | 0.2 | (0.36) | Pt50 | -200 ... +850 (-328 ... +1562) | 10 | (18) | 0.15 | (0.27) | Pt100 ... Pt200 | -200 ... +850 (-328 ... +1562) | 10 | (18) | 0.1 | (0.18) | Pt500 | -200 ... +850 (-328 ... +1562) | 10 | (18) | 0.15 | (0.27) | Pt1000 | -200 ... +350 (-328 ... +662) | 10 | (18) | 0.15 | (0.27) | to JIS C1604-81 | | | | | | Pt25 | -200 ... +649 (-328 ... +1200) | 10 | (18) | 0.2 | (0.36) | Pt50 | -200 ... +649 (-328 ... +1200) | 10 | (18) | 0.15 | (0.27) | Pt100 ... Pt200 | -200 ... +649 (-328 ... +1200) | 10 | (18) | 0.1 | (0.18) | Pt500 | -200 ... +649 (-328 ... +1200) | 10 | (18) | 0.15 | (0.27) | Pt1000 | -200 ... +350 (-328 ... +662) | 10 | (18) | 0.15 | (0.27) | Ni 25 to Ni1000 | -60 ... +250 (-76 ... +482) | 10 | (18) | 0.1 | (0.18) |
Resistance-based sensors Input | Measuring range | Min. measured span | Digital accuracy |
---|
| Ω | Ω | Ω | Resistance | 0 ... 390 | 5 | 0.05 | Resistance | 0 ... 2200 | 25 | 0.25 |
Thermocouples Input | Measuring range | Min. measured span | Digital accuracy |
---|
| °C | (°F) | °C | (°F) | °C | (°F) | Type B | 0 ... 1820 | (32 ... 3308) | 100 | (180) | 21) | (3.60)1) | Type C (W5) | 0 ... 2300 | (32 ... 4172) | 100 | (180) | 2 | (3.60) | Type D (W3) | 0 ... 2300 | (32 ... 4172) | 100 | (180) | 12) | (1.80)2) | Type E | -200 ... +1000 | (-328 ... +1832) | 50 | (90) | 1 | (1.80) | Type J | -210 ... +1200 | (-346 ... +2192) | 50 | (90) | 1 | (1.80) | Type K | -230 ... +1370 | (-382 ... +2498) | 50 | (90) | 1 | (1.80) | Type L | -200 ... +900 | (-328 ... +1652) | 50 | (90) | 1 | (1.80) | Type N | -200 ... +1300 | (-328 ... +2372) | 50 | (90) | 1 | (1.80) | Type R | -50 ... +1760 | (-58 ... +3200) | 100 | (180) | 2 | (3.60) | Type S | -50 ... +1760 | (-58 ... +3200) | 100 | (180) | 2 | (3.60) | Type T | -200 ... +400 | (-328 ... +752) | 40 | (72) | 1 | (1.80) | Type U | -200 ... +600 | (-328 ... +1112) | 50 | (90) | 2 | (3.60) |
1) The digital accuracy in the range 0 to 300 °C (32 to 572 °F) is 3 °C (5.4 °F). 2) The digital accuracy in the range 1750 to 2300 °C (3182 to 4172 °F) is 2 °C (3.6 °F). mV sensor Input | Measuring range | Min. measured span | Digital accuracy |
---|
| mV | mV | μV | mV sensor | -10 ... +70 | 2 | 40 | mV sensor | -100 ... +1100 | 20 | 400 |
The digital accuracy is the accuracy after the analog/digital conversion including linearization and calculation of the measured value. An additional error is generated in the output current 4 to 20 mA as a result of the digital/analog conversion of 0,1 % of the set span (digital-analog error). The total error under reference conditions at the analog output is the sum from the digital error and the digital-analog error (poss. with the addition of cold junction errors in the case of thermocouple measurements).
|
|
|
|
|
SITRANS TH200
|
|
Mã sản phẩm:
7NG3211-1NN00
Tên sản phẩm:
SITRANS TH200
Input | | Resistance thermometer | | Measured variable | Temperature | Sensor type | | | Pt25 … Pt1000 | - To JIS C 1604; a = 0.00392 K-1
| Pt25 … Pt1000 | | Ni25 … Ni1000 | | over special characteristic (max. 30 points) | Sensor factor | 0.25 ... 10 (adaptation of the basic type, e.g. Pt100 to version Pt25 ... Pt1000) | Units | °C or °F | Connection | | | 1 resistance thermometer (RTD) in 2-wire, 3-wire or 4-wire system | - Generation of average value
| 2 identical resistance thermometers in 2-wire system for generation of average temperature | | 2 identical resistance thermometers (RTD) in 2-wire system (RTD 1 – RTD 2 or RTD 2 – RTD 1) | Interface | | | Parameterizable line resistance ≤ 100 Ω (loop resistance) | | No balancing required | | No balancing required | Sensor current | ≤ 0.45 mA | Response time | ≤ 250 ms for 1 sensor with open-circuit monitoring | Open-circuit monitoring | can be switched off | Short-circuit monitoring | can be switched off (value is adjustable) | Measuring range | Parameterizable (see table "Digital measuring errors") | Min. measured span | 10 °C (18 °F) | Characteristic curve | Temperature-linear or special characteristic | Resistance-based sensors | | Measured variable | Actual resistance | Sensor type | Resistance-based, potentiometers | Units | Ω | Connection | | | 1 resistance-based sensor (R) in 2-wire, 3-wire or 4-wire system | - Generation of average value
| 2 resistance-based sensors in 2-wire system for generation of average value | | 2 resistance thermometers in 2-wire system (R1 – R2 or R2 – R1) | Interface | | | Parameterizable line resistance ≤ 100 Ω (loop resistance) | | No balancing required | | No balancing required | Sensor current | ≤ 0.45 mA | Response time | ≤ 250 ms for 1 sensor with open-circuit monitoring | Open-circuit monitoring | can be switched off | Short-circuit monitoring | can be switched off (value is adjustable) | Measuring range | Parameterizable, max. 0 ... 2200 Ω (see Table "Digital measuring errors") | Min. measured span | 5 Ω ... 25 Ω (see Table "Digital measuring errors") | Characteristic curve | Resistance-linear or special characteristic | Thermocouples | | Measured variable | Temperature | Sensor type (thermocouples) | | | Pt30Rh-Pt6Rh to DIN IEC 584 | | W5 %-Re acc. to ASTM 988 | | W3 %-Re acc. to ASTM 988 | | NiCr-CuNi to DIN IEC 584 | | Fe-CuNi to DIN IEC 584 | | NiCr-Ni to DIN IEC 584 | | Fe-CuNi to DIN 43710 | | NiCrSi-NiSi to DIN IEC 584 | | Pt13Rh-Pt to DIN IEC 584 | | Pt10Rh-Pt to DIN IEC 584 | | Cu-CuNi to DIN IEC 584 | | Cu-CuNi to DIN 43710 | Units | °C or °F | Connection | | | 1 thermocouple (TC) | - Generation of average value
| 2 thermocouples (TC) | | 2 thermocouples (TC) TC1 – TC2 or TC2 – TC1) | Response time | ≤ 250 ms for 1 sensor with open-circuit monitoring | Open-circuit monitoring | can be switched off | Cold junction compensation | | | With integrated Pt100 resistance thermometer | | With external Pt100 IEC 60571 (2-wire or 3-wire connection) | | Cold junction temperature can be set as fixed value | Measuring range | Parameterizable (see table "Digital measuring errors") | Min. measured span | Min. 50 ... 100 °C (90 ... 180 °F) (see table "Digital measuring errors") | Characteristic curve | Temperature-linear or special characteristic | mV sensor | | Measured variable | DC voltage | Sensor type | DC voltage source (DC voltage source possible over an externally connected resistor) | Units | mV | Response time | ≤ 250 ms for 1 sensor with open-circuit monitoring | Open-circuit monitoring | can be switched off | Short-circuit monitoring | can be switched off (value is adjustable) | Measuring range | -10 ... +70 mV -100 +1100 mV | Min. measured span | 2 mV or 20 mV | Overload capability of the input | -1.5 ... +3.5 V DC | Input resistance | ≥ 1 MΩ | Characteristic curve | Voltage-linear or special characteristic | Output | | Output signal | 4 ... 20 mA, 2-wire | Auxiliary power supply | 11 ... 35 V DC (to 30 V with EEx) | Max. load | (Uaux – 11 V)/0.023 A | Overrange | 3.6 ... 23 mA, infinitely adjustable (default range: 3.80 mA ... 20.50 mA) | Error signal (e.g. in the event of sensor breakage) | 3.6 ... 23 mA, infinitely adjustable (default value: 22.8 mA) | Sample cycle | 0.25 s nominal | Damping | Software filter 1st order 0 ... 30 s (parameterizable) | Protection | Against reversed polarity | Electrically isolated | Input against output (1 kVeff) | Measuring accuracy | | Digital measuring errors | See Table "Digital measuring errors" | Reference conditions | | | 24 V ± 1 % | | 500 Ω | | 23 °C | | > 5 min | Error in the analog output (digital/analog converter) | < 0.1 % of span | Error due to internal cold junction | < 0.5 °C (0.9 °F) | Temperature effect | < 0.1 % of max. span/10 °C (18 °F) | Auxiliary power supply effect | < 0.005 % of span/V | Effect of load impedance | < 0.012 % of span/100 Ω | Long-term drift | | | < 0.02 % of max. span | | < 0.03 % of max. span | | < 0.04 % of max. span | Conditions of use | | Ambient conditions | | Ambient temperature range | -40 ... +85 °C (-40 ... 185 °F) | Storage temperature range | -40 ... +85 °C (-40 ... 185 °F) | Relative humidity | < 98 %, with condensation | Electromagnetic compatibility | acc. to EN 61326 and NE21 | Construction | | Material | Molded plastic | Weight | 50 g (0.11 lb) | Dimensions | See "Dimensional drawings" | Cross-section of cables | Max. 2.5 mm² (AWG 13) | Degree of protection to IEC 60529 | | | IP40 | | IP00 | Certificates and approvals | | Explosion protection ATEX | | EC type test certificate | PTB 05 ATEX 2040X | - "Intrinsic safety" type of protection
| II 1 G Ex ia IIC T6/T4 II 2(1) G Ex ib/ia IIC T6/T4 | - "Operating equipment that is non-ignitable and has limited energy" type of protection
| II 3 G Ex nL IIC T6/T4 II 3 G Ex nA IIC T6/T4 | Explosion protection: FM for USA | | | FM 3024169 | | IS/Cl I, II, III/Div 1/GP ABCDEFG T6, T5, T4 IS/Cl I/ZN 0/AEx ia IIC T6, T5, T4 NI/Cl I, II, III/Div 2/GP ABCDFG T6, T5, T4 NI/Cl I/ZN 2/IIC T6, T5, T4 | Explosion protection to FM for Canada (cFMUS) | | | FM 3024169C | | IS/Cl I/ZN 0/Ex ia IIC T6, T5, T4 NI/Cl I/ZN 2/Ex nAL IIC T6, T5, T4 | Software requirements for SIPROM T | | PC operating system | Windows ME, 2000 and XP; also Windows 95, 98 and 98 SE, but only in connection with RS 232 modem. |
Factory setting: - Pt100 (IEC 751) with 3-wire circuit
- Measuring range: 0 ... 100 °C (32 ... 212 °F)
- Fault current: 22.8 mA
- Sensor offset: 0 °C (0 °F)
- Damping 0.0 s
Digital measuring errorsResistance thermometer Input | Measuring range | Min. measured span | Digital accuracy |
---|
| °C (°F) | °C | (°F) | °C | (°F) | to IEC 60751 | | | | | | Pt25 | -200 ... +850 (-328 ... +1562) | 10 | (18) | 0.2 | (0.36) | Pt50 | -200 ... +850 (-328 ... +1562) | 10 | (18) | 0.15 | (0.27) | Pt100 ... Pt200 | -200 ... +850 (-328 ... +1562) | 10 | (18) | 0.1 | (0.18) | Pt500 | -200 ... +850 (-328 ... +1562) | 10 | (18) | 0.15 | (0.27) | Pt1000 | -200 ... +350 (-328 ... +662) | 10 | (18) | 0.15 | (0.27) | to JIS C1604-81 | | | | | | Pt25 | -200 ... +649 (-328 ... +1200) | 10 | (18) | 0.2 | (0.36) | Pt50 | -200 ... +649 (-328 ... +1200) | 10 | (18) | 0.15 | (0.27) | Pt100 ... Pt200 | -200 ... +649 (-328 ... +1200) | 10 | (18) | 0.1 | (0.18) | Pt500 | -200 ... +649 (-328 ... +1200) | 10 | (18) | 0.15 | (0.27) | Pt1000 | -200 ... +350 (-328 ... +662) | 10 | (18) | 0.15 | (0.27) | Ni 25 to Ni1000 | -60 ... +250 (-76 ... +482) | 10 | (18) | 0.1 | (0.18) |
Resistance-based sensors Input | Measuring range | Min. measured span | Digital accuracy |
---|
| Ω | Ω | Ω | Resistance | 0 ... 390 | 5 | 0.05 | Resistance | 0 ... 2200 | 25 | 0,25 |
Thermocouples Input | Measuring range | Min. measured span | Digital accuracy |
---|
| °C | (°F) | °C | (°F) | °C | (°F) | Type B | 0 ... 1820 | (32 ... 3308) | 100 | (180) | 21) | (3.60)1) | Type C (W5) | 0 ... 2300 | (32 ... 4172) | 100 | (180) | 2 | (3.60) | Type D (W3) | 0 ... 2300 | (32 ... 4172) | 100 | (180) | 12) | (1.80)2) | Type E | -200 ... +1000 | (-328 ... +1832) | 50 | (90) | 1 | (1.80) | Type J | -210 ... +1200 | (-346 ... +2192) | 50 | (90) | 1 | (1.80) | Type K | -230 ... +1370 | (-382 ... +2498) | 50 | (90) | 1 | (1.80) | Type L | -200 ... +900 | (-328 ... +1652) | 50 | (90) | 1 | (1.80) | Type N | -200 ... +1300 | (-328 ... +2372) | 50 | (90) | 1 | (1.80) | Type R | -50 ... +1760 | (-58 ... +3200) | 100 | (180) | 2 | (3.60) | Type S | -50 ... +1760 | (-58 ... +3200) | 100 | (180) | 2 | (3.60) | Type T | -200 ... +400 | (-328 ... +752) | 40 | (72) | 1 | (1.80) | Type U | -200 ... +600 | (-328 ... +1112) | 50 | (90) | 2 | (3.60) |
1) The digital accuracy in the range 0 to 300 °C (32 to 572 °F) is 3 °C (5.4 °F). 2) The digital accuracy in the range 1750 to 2300 °C (3182 to 4172 °F) is 2 °C (3.6 °F). mV sensor Input | Measuring range | Min. measured span | Digital accuracy |
---|
| mV | mV | μV | mV sensor | -10 ... +70 | 2 | 40 | mV sensor | -100 ... +1100 | 20 | 400 |
The digital accuracy is the accuracy after the analog/digital conversion including linearization and calculation of the measured value. An additional error is generated in the output current 4 to 20 mA as a result of the digital/analog conversion of 0.1 % of the set span (digital-analog error). The total error under reference conditions at the analog output is the sum from the digital error and the digital-analog error (poss. with the addition of cold junction errors in the case of thermocouple measurements).
|
|
|
|
|
SITRANS TH400, fieldbus transmitters
|
|
Mã sản phẩm:
7NG3214/7NG3215
Tên sản phẩm:
SITRANS TH400, fieldbus transmitters
Input | | Analog-to-digital conversion | | | < 50 ms | | 24-bit | Resistance thermometer | | Pt25 ... Pt1000 to IEC 60751/JIS C 1604 | | | -200 ... +850 °C (-328 ... +1562 °F) | Ni25 ... Ni1000 to DIN 43760 | | | -60 ... +250 °C (-76 ... +482 °F) | Cu10 ... Cu1000, α = 0.00427 | | | -50 ... +200 °C (-58 ... +392 °F) | Line resistance per sensor cable | Max. 50 Ω | Sensor current | Nominal 0.2 mA | Sensor fault detection | | | Yes | - Sensor short-circuit detection
| Yes, < 15 Ω | Resistance-based sensors | | Measuring range | 0 Ω ... 10 kΩ | Line resistance per sensor cable | Max. 50 Ω | Sensor current | Nominal 0.2 mA | Sensor fault detection | | | Yes | - Sensor short-circuit detection
| Yes, < 15 Ω | Thermocouple | | to IEC 584 | Measuring range | | 400 ... 1820 °C (752 ... 3308 °F) | | -100 ... +1000 °C (-148 ... +1832 °F) | | -100 ... +1000 °C (-148 ... +1832 °F) | | -100 ... +1200 °C (-148 ... +2192 °F) | | -180 ... +1300 °C (-292 ... +2372 °F) | | -50 ... +1760 °C (-58 ... +3200 °F) | | -50 ... +1760 °C (-58 ... +3200 °F) | | -200 ... +400 °C (-328 ... +752 °F) | to DIN 43710 | | | -200 ... +900 °C (-328 ... +1652 °F) | | -200 ... +600 °C (-328 ... +1112 °F) | to ASTM E988-90 | | | 0 ... 2300 °C (32 ... +4172 °F) | | 0 ... 2300 °C (32 ... +4172 °F) | External cold junction compensation | -40 ... +135 °C (-40 ... +275 °F) | Sensor fault detection | | | Yes | - Sensor short-circuit detection
| Yes, < 3 mV | - Sensor current in the event of open-circuit monitoring
| 4 μA | mV sensor - voltage input | | Measuring range | -800 ... +800 mV | Input resistance | 10 MΩ | Output | | Filter time (programmable) | 0 ... 60 s | Update time | < 400 ms |
Measuring accuracy | | |
---|
Accuracy is defined as the higher value of general values and basic values. | General values | | | Type of input | Absolute accuracy | Temperature coefficient | All | ≤ ±0.05 % of measured value | ≤ ±0.002 % of measured value / °C | Basic values | | | Type of input | Basic accuracy | Temperature coefficient | Pt100 and Pt1000 | ≤± 0.1 °C | ≤± 0.002 °C / °C | Ni100 | ≤± 0.15 °C | ≤± 0.002 °C / °C | Cu10 | ≤± 1.3 °C | ≤± 0.02 °C / °C | Resistance-based sensors | ≤± 0.05 °Ω | ≤± 0.002 °Ω / °C | Voltage source | ≤± 10 μV | ≤± 0.2 % μV / °C | Thermocouple, type: E, J, K, L, N, T, U | ≤± 0.5 °C | ≤± 0.01 °Ω / °C | Thermocouple, type: B, R, S, W3, W5 | ≤± 1 °C | ≤± 0.025 % °C / °C | Cold junction compensation | ≤± 0.5 °C | | Reference conditions | | | Warming-up time | 30 s | | Signal-to-noise ratio | Min. 60 dB | | Calibration condition | 20 ... 28 °C (68 ... 82 °F) | |
Conditions of use | | Ambient conditions | | Permissible ambient temperature | -40 ... +85 °C (-40 ... +185 °F) | Permissible storage temperature | -40 ... +85 °C (-40 ... +185 °F) | Relative humidity | ≤ 98 %, with condensation | Electrically isolated | | | Input against output 1 kVeff | | Input against output 500 Veff | Mechanical testing | | - Vibrations (DIN class B) to
| IEC 60068-2-6 and IEC 60068-2-64 4 g/2 ... 100 Hz | Electromagnetic compatibility | | EMC noise voltage influence | < ±0.1 % of span | Extended EMC noise immunity: NAMUR NE 21, criterion A, Burst | < ±1 % of span | EMC 2004/108/EC Emission and Noise Immunity to | EN 61326 | Construction | | Material | Molded plastic | Weight | 55 g (0.12 lb) | Dimensions | See Dimensional drawings | Cross-section of cables | Max. 2.5 mm2 (AWG 13) | Degree of protection | | | IP40 | | IP00 | Auxiliary power supply | | Power supply | | - Standard, Ex "nA", Ex "nL", NI
| 9.0 ... 32 V DC | | 9.0 ... 30 V DC | - In FISCO/FNICO installations
| 9.0 ... 17.5 V DC | Power consumption | < 11 mA | Max. increase in power consumption in the event of a fault | < 7 mA |
Certificates and approvals | | Explosion protection ATEX | | EC type test certificate | KEMA 06 ATEX 0264 X | - "Intrinsic safety" type of protection
| II 1 GD EEx ia IIC T4 ... T6 T65 °C ... T105 °C II 2(1) GD EEx ib [ia] IIC T4 ... T6 T65 °C ... T105 °C | EC type test certificate | KEMA 06 ATEX 0263 X | - Type of protection for "equipment is non-arcing"
| II 3 G EEx nA [nL] IIC T4 ... T6 II 3 G EEx nL IIC T4 ... T6 | Explosion protection: FM for USA | | | FM 3027985 | | - IS/Cl I/Div 1/Groups ABCD T4, T5, T6, FISCO
- IS/Cl I/ZN 0/AEx ia, IIC T4, T5, T6, FISCO
- NI/Cl I/Div 2/Groups ABCD T4, T5, T6, FNICO
| Explosion protection CSA for Canada | | | CSA 1861385 | | - IS/Cl I/Div 1/Groups ABCD T4, T5, T6
- Ex ia IIC T4/T5/T6
Ex ib [ia] IIC T4/T5/T6 - Cl I/Div 2/Groups ABCD, T4, T5, T6
- Ex nA IIC T4/T5/T6
Cl I/ZN 2/AEx nA II T4, T5, T6
| Communication | | Parameterization interface | | | | | Profile 3.0 | | 126 | - FOUNDATION fieldbus connection
| | | FF protocol | | Basic or LAS | | ITK 4.6 | | 2 x analog and 1 x PID | Factory setting | only for SITRANS TH400 PA | | Sensor | Pt100 (IEC) | Type of connection | 3-wire circuit | Unit | °C | Failure mode | Last valid value | Filter time | 0 s | PA address | 126 | PROFIBUS Ident No. | Manufacturer-specific | only for SITRANS TH400 FF | | Sensor | Pt100 (IEC) | Type of connection | 3-wire circuit | Unit | °C | Failure mode | Last valid value | Filter time | 0 s | Node address | 22 |
|
|
|
|
|
SITRANS TF2, digital display thermometer
|
|
Mã sản phẩm:
7NG3140
Tên sản phẩm:
SITRANS TF2, digital display thermometer
Measuring principle | | Resistance thermometer | Pt100 class B acc. to DIN IEC 751 | Input | | Measured variable | Temperature | Max. measuring range | -50 °C ... +200 °C (-58 ... +392 °F) | Min. measured span | 50 K (90 °F) | Output | | Output signal | 4 ... 20 mA, 2-wire | Lower current limit | Min. 3.6 mA | Upper current limit | Max. 23 mA | Output protected against | Reversed polarity, overvoltage and short-circuiting | Max. load | (UH – 12 V) / 0.023 A | Characteristic | Temperature-linear | Measuring accuracy | | Error in measurement at 23 °C ± 5 K (73.4 ± 9 °F) | < ± (0.45 K + 0.2 % of full-scale value in K + 1 digit in K) (< ± (0.81 °F + 0.2 % of full-scale valuein °F + 1 digit in F) | Measuring cycle time | ≤ 100 ms | Temperature effect | < ± 0.15 %/10 K (< ± 0.15 %/18 °F) | Power supply effect | < ±0,01 % of full-scale value/V | Vibration influence | < ±0.05 %/g to 500 Hz in all directions (to IEC 68‑2‑64) | Rated operating conditions | | Ambient conditions | | Ambient temperature | -25 ... +85 °C (-13 ... +185 °F) | Temperature range for best readability | -10 ... +70 °C (14 ... 158 °F) | Storage temperature | -40 ... +85 °C (-40 ... +185 °F) | Degree of protection | IP65 to EN 60529 | Electromagnetic compatibility | EN 61326/A2 Appendix A (2001) | Displays and controls | | Display | LCD, max. 5 digits, digit height 9 mm (0.354 inch) | Resolution at max. measuring range | 0.01 °C (0.01 °F) | Decimal point | Freely parameterizable | Limit values | Freely parameterizable | Limit violation display | Red LED and message on LCD (↑ symbol /↓ symbol in case of limit violation in upward / downward direction) | Parameterization | With 3 keys | Units | mA or % or Ω or physical variable: °C, °F, °R, K | Damping | Between 0.1 and 100 s (increment: 0.1 s) freely parameterizable | Design | | Weight | ≈ 0.7 kg (≈ 1.54 lb) | Non-wetted parts materials | | | Diam. 80 mm (diam. 3.15 inch), stainless steel, mat. No. 1.4016 | | Stainless steel, mat. No. 1.4016 with glass | Wetted parts materials | | | To DIN 43772 form 8 (March 2000), Ø 14 x 1.5 mm (Ø 0.55 x 0.06 inch) | | Stainless steel (mat. No. 1.4571/316Ti) | - Protective tube screw socket
| G½B to DIN 3852-2 form A or ½“-14 NPT | | Stainless steel (mat. No. 1.4571/316Ti) | Measuring insert | Length to fit the ordered protective tube, stainless steel | Connection of display to the protective tube | Radial (type A), can be swiveled by max. ±120° (α) | | axial (type B), can be swiveled by max. ±360° | Length of the protective tube(U1) | See Ordering data | Electrical connection | Using 2-pole plug connector made of plastic with M16x1.5‑cable entry to EN 175301‑803A, ½"-14 NPT | Power supply | | Terminal voltage on temperature transmitter (UH) | 12 ... 30 V DC | Operating limits | | Pressure | Max. 40 bar (580 psi) |
|
|
|
|
|
SITRANS TW, four-wire system, universal, HART
|
|
Mã sản phẩm:
7NG3242
Tên sản phẩm:
SITRANS TW, four-wire system, universal, HART
Input | | Selectable filters to suppress the line frequency | 50 Hz, 60 Hz, also 10 Hz for special applications (line frequency filter is similar with measuring frequency) | Resistance thermometer | | Measured variable | Temperature | Measured range | Parameterizable | Measured span | Min. 25 °C (45 °F) x 1/scaling factor | Sensor type | | | Pt100 (DIN IEC 751) | | Pt100 (JIS C1604-81) | | Ni100 (DIN 43760) | - Special type (RRTD ≤ 500 Ω)
| Multiples or parts of the defined characteristic values can be parameterized (e.g. Pt500, Ni120) | Voltage measurement | Temperature-linear, resistance-linear or customer-specific | Type of connection | - Normal connection
- Sum or parallel connection
- Mean-value or differential connection
| Connection | 2, 3 or 4-wire circuit | Measuring range limits | Depending on type of connected thermometer (defined range of resistance thermometer) | Sensor breakage monitoring | Monitoring of all connections for open-circuit (function can be switched off) | Sensor short-circuit monitoring | Parameterizable response threshold (function can be switched off) | Resistance-based sensors, potentiometers | | Measured variable | Ohmic impedance | Measured range | Parameterizable | Measured span | Min. 10 Ω | Voltage measurement | Resistance-linear or customer-specific | Type of connection | - Normal connection
- Differential connection
- Mean-value connection
| Connection | 2, 3 or 4-wire circuit | Input range | 0 ... 6000 Ω; with mean-value and difference circuits: 0 ... 3000 Ω | Sensor breakage monitoring | Monitoring of all connections for open-circuit (function can be switched off) | Sensor short-circuit monitoring | Parameterizable response threshold (function can be switched off) | Thermocouple elements | | Measured variable | Temperature | Measured range | Parameterizable | Measured span | Min. 50 °C (32.22 °C) x 1/scaling factor | Measuring range limits | Depend. on type of thermocouple element | Thermocouple | Type B: Pt30 %Rh/Pt6 %Rh (DIN IEC 584) | | Type C W5 %-Re (ASTM 988) | | Type D W3 %-Re (ASTM 988) | | Type E: NiCr/CuNi (DIN IEC 584) | | Type J: Fe/CuNi (DIN IEC 584) | | Type K: NiCr/Ni (DIN IEC 584) | | Type L Fe-CuNi (DIN 43710) | | Type N: NiCrSi-NiSi (DIN IEC 584) | | Type R: Pt13 %Rh/Pt (DIN IEC 584) | | Type S: Pt10 %Rh/Pt (DIN IEC 584) | | Type T: Cu/CuNi (DIN IEC 584) | | Type U: Cu/CuNi (DIN 43710) | | Special type (-10 mV ≤ UTC ≤ 100 mV) | Voltage measurement | Temperature-linear, voltage-linear or customer-specific | Type of connection | - Normal connection
- Sum connection
- Mean-value connection
- Differential connection
| Cold junction compensation | None, internal measurement, external measurement or predefined fixed value | Sensor breakage monitoring | Function can be switched off | mV sensors | | Measured variable | DC voltage | Measured range | Parameterizable | Measured span | Min. 4 mV | Input range | -120 ... +1000mV | Voltage measurement | Voltage-linear or customer-specific | Overload capacity of inputs | Max. ± 3.5 V | Input resistance | ≥ 1 Ω | Sensor current | Approx. 180 μA | Sensor breakage monitoring | Function can be switched off | V sources | | Measured variable | DC voltage | Measured range | Parameterizable | Voltage measurement | Voltage-linear or customer-specific | Input range/min. span | | - Devices with 7NG3242-xxxx1or 7NG3242-xxxx 0 with U/I plug
| -1.2 V ... +10 V 0.04 V | - Devices with 7NG3242-xxxx2
| -12 V ... +100 V 0.4 V | - Devices with 7NG3242-xxxx3
| -120 V ... +140 V 4.0 V | Sensor breakage monitoring | Not possible | μA, mA sources | | Measured variable | DC voltage | Measured range | Parameterizable | Voltage measurement | Current-linear or customer- specific | Input range/min. span | | - Devices with 7NG3242-xxxx4
| -12 μA ... +100 μA/0.4 μA | - Devices with 7NG3242-xxxx5
| -120 μA ... +1000 μA/4 μA | - Devices with 7NG3242-xxxx6
| -1.2 mA ... +10 mA 0.04 mA | - Devices with 7NG3242-xxxx7or 7NG3242-xxxx 0 with U/I plug
| -12 mA ... +100 mA 0.4 mA | - Devices with 7NG3242-xxxx8
| -120 mA ... +1000 mA 4 mA | Sensor breakage monitoring | Not possible | Output | | Output signal | Load-independent direct current 0/4 ... 20 mA, can be switched to load-independent DC voltage 0/2 ... 10 V using plug-in jumpers. | Current 0/4 ... 20 mA | | | -0.5 ... +23.0 mA, continuously adjustable | - Output range following sensor fault
| -0.5 ... +23.0 mA, continuously adjustable | | ≤ 650 Ω | | ≤ 30 V | Voltage 0/2 ... 10 V | | | -0.25 ... +10.75 V, continuously adjustable | - Output range following sensor fault
| -0.25 ... +10.75 V, continuously adjustable | | ≥ 1 kΩ | | ≤ 10 nF | | ≤ 100 mA (not permanently short-circuit-proof) | | | - Adjustable time constant T63
| 0 ... 100 s, in steps of 0.1 s | - Current source/voltage source
| Continuously adjustable within the total operating range | Sensor fault/limit signalling | By operation indicator, relay output or HART interface | Operation indicator | Flashing signal | | Flashing frequency 5 Hz | | Flashing frequency 1 Hz | Relay output | Either as NO or NC contact with 1 changeover contact | | ≤ 150 W, ≤ 625 VA | | ≤ 125 V DC, ≤ 250 V AC | | ≤ DC 2.5 A | Overrange | Signalling of sensor or line breakage and sensor short-circuit | Limit monitoring | | | 0 ... 10 s | - Monitoring functions of limit module
| - Sensor fault (breakage and/or short-circuit)
- Lower and upper limit
- Window (combination of lower and upper limits)
- Limit and sensor fault detection can be combined
| | Parameterizable between 0 and 100 % of measuring range | Power supply | | Universal power supply unit | 115/230 V AC/DC or 24 V AC/DC | Tolerance range for power supply | | | 80 ... 300 V DC; 90 ... 250 V AC | | 18 ... 80 V DC; 20.4 ... 55.2 V AC (in each case interruption-resistant up to 20 ms in the complete tolerance range) | Tolerance range for mains frequency | 47 ... 63 Hz | Power consumption with | | | ≤ 5 VA | | ≤ 5 W | | ≤ 5 VA | | ≤ 5 W | Electrical isolation | | Electrically isolated circuits | Input, output, power supply and sensor fault/limit monitoring output are electrically isolated from one another. The HART interface is electrically connected to the output. | Working voltage between all electrically isolated circuits | The voltage U eff between any two terminals must not exceed 300 V | Measuring accuracy | | Measurement error | | - Error in the internal cold junction
| ≤ 3 °C ± 0,1 °C/10 °C (≤ 5.4 °F ± 0,18 °F/18 °F) | - Error of external cold junction terminal 7NG3092-8AV
| ≤ 0.5 °C ± 0,1 °C/10 °C (≤ 0.9 °F ± 0.18 °F/18 °F) | | See "Digital error" | | ≤ 0.05 % of span in addition to digital error | Influencing effects (referred to the digital output) | Compared to the max. span: | | ≤ 0.08 %/10 °C (≤ 0.08 %/18 °F) ≤ 0.2 % in the range -10 ... +60 °C (14 ... 140 °F) | | ≤ 0.1 %/year | Influencing effects referred to the analog output IAN or UAN | Compared to the span: | | ≤ 0.08 %/10°C (≤ 0.08 %/18 °F) ≤ 0.2 % in the range -10 ... +60 °C (14 ... 140 °F) | | ≤ 0.05 %/10 V | | ≤ 0.05 % with change from 50 ... 650 Ω | | ≤ 0.1 % with change in load current from 0 … 10 mA | - Long-term drift (start-of-scale value, span)
| ≤ 0.03 %/month | Response time (T63without electrical damping) | ≤ 0.2 s | Electromagnetic compatibility | According to EN 61 326 and NAMUR NE21 | Certificate and approvals | | ATEX | To DIN EN 50014: 1997, EN 50020: 1994 | Intrinsic safety to EN 50 020 | | | II (1) G D [EEx ia/ib ] IIB | | II (1) G D [EEx ia/ib ] IIC | EC-Type Examination Certificate | TÜV (German Technical Inspectorate) 01 ATEX 1675 | Rated conditions | | Installation conditions | | Location (for devices with explosion protection) | | | Outside the potentially explosive atmosphere | | Within the potentially explosive atmosphere zone 1 (also in zone 0 in conjunction with the prescribed protection requirements for the sensor) | Ambient conditions | | Permissible ambient temperature | -25 ... +70 °C (-13 ... +158 °F) | Permissible storage temperature | -40 ... +85 °C (-40 ... +185 °F) | Climatic class | | | 5 ... 95 %, no condensation | Design | | Weight | Approx. 0.24 kg (0.53 lb) | Enclosure material | PBT, glass-fibre reinforced | Degree of protection to IEC 529 | IP20 | Degree of protection to VDE 0100 | Protection class I | Type of installation | 35-mm top hat rail (1.38 inch) (DIN EN 50022) or 32-mm G-type rail (1.26 inch) (DIN EN 50035) | Electrical connection / process connection | Screw plug connectors, max. 2.5 mm² (0.01 inch²) | Parameterization interface | | Protocol | HART, version 5.9 | Load with connection of | | | 230 ... 650 Ω | | 230 ... 500 Ω | Software for PC/laptop | SIMATIC PDM version V5.1 and later |
Digital errorResistance thermometer Input | Measured range | Max. permissible line resistance | Digital error |
---|
| °C (°F) | Ω | °C (°F) | DIN IEC 751 | | | | | -200 ... +850 (‑328 ... +1562) | 20 | 3.0 (5.4) | | -200 ... +850 (‑328 ... +1562) | 50 | 0.6 (1.1) | | -200 ... +850 (‑328 ... +1562) | 100 | 0.3 (0.5) | | -200 ... +850 (‑328 ... +1562) | 100 | 0.6 (1.1) | | -200 ... +850 (‑328 ... +1562) | 100 | 1.0 (1.8) | | -200 ... +850 (‑328 ... +1562) | 100 | 1.0 (1.8) | JIS C 1604-81 | | | | | -200 ... +649 (‑328 ... +1200) | 20 | 3.0 (5.4) | | -200 ... +649 (‑328 ... +1200) | 50 | 0.6 (1.1) | | -200 ... +649 (‑328 ... +1200) | 100 | 0.3 (0.5) | DIN 43760 | | | | | -60 ... +250 (‑76 ... +482) | 50 | 0.3 (0.5) | | -60 ... +250 (‑76 ... +482) | 100 | 0.3 (0.5) | | -60 ... +250 (‑76 ... +482) | 100 | 0.3 (0.5) | | -60 ... +250 (‑76 ... +482) | 100 | 0.3 (0.5) |
Resistance-based sensors Input | Measured range | Max. permissible line resistance | Digital error |
---|
| Ω | Ω | Ω | Resistance (linear) | 0 ... 24 | 5 | 0.08 | | 0 ... 47 | 15 | 0.06 | | 0 ... 94 | 30 | 0.06 | | 0 ... 188 | 50 | 0.08 | | 0 ... 375 | 100 | 0.1 | | 0 ... 750 | 100 | 0.2 | | 0 ... 1500 | 75 | 1.0 | | 0 ... 3000 | 100 | 1.0 | | 0 ... 6000 | 100 | 2.0 |
Thermocouple elements Input | Measured range | Digital error 1) |
---|
| °C (°F) | °C (°F) | Type B | 0 ... +1820 (+32 ... +3308) | 3 (5.4) | Type C | 0 ... +2300 (+32 ... +4172) | 2 (3.6) | Type D | 0 ... +2300 (+32 ... +4172) | 1 (1.8) | Type E | -200 ... +1000 (‑328 ... +1832) | 1 (1.8) | Type J | -210 ... +1200 (‑346 ... +2192) | 1 (1.8) | Type K | -200 ... +1372 (‑328 ... +2501) | 1 (1.8) | Type L | -200 ... +900 (‑328 ... +1652) | 2 (3.6) | Type N | -200 ... +1300 (‑328 ... +2372) | 1 (1.8) | Type R | -50 ... +1760 (‑58 ... +3200) | 2 (3.6) | Type S | -50 ... +1760 (‑58 ... +3200) | 2 (3.6) | Type T | -200 ... +400 (‑328 ... +752) | 1 (1.8) | Type U | -200 ... +600 (‑328 ... +1112) | 2 (3.6) |
1) Accuracy data refer to the largest error in the complete measuring range Voltage/current sources Input | Measuring range mV | Digital error μV |
---|
mV sources (linear) | -1 ... +16 | 35 | | -3 ... +32 | 20 | | -7 ... +65 | 20 | | -15 ... +131 | 50 | | -31 ... +262 | 100 | | -63 ... +525 | 200 | | -120 ... +1000 | 300 | | Measuring range V | Digital error mV | V sources (linear) | -1,2 ... +10 | 3 | | -12 ... +100 | 30 | | -120 ... +140 | 300 | | Measuring range μA/mA | Digital error μA | μA/mA sources (linear) | -12 ... 100 μA | 0,05 | | -120 ... +1000 μA | 0,5 | | -1,2 ... +10 mA | 5 | | -12 ... +100 mA | 50 | | -120 ... +1000 mA | 500 |
|
|
|
|
|
SITRANS TH100, two-wire system (Pt100)
|
|
Mã sản phẩm:
7NG3211-0NN00
Tên sản phẩm:
SITRANS TH100, two-wire system (Pt100)
SITRANS TH100 | | Input | | Resistance thermometer | | Measured variable | Temperature | Sensor type | PT100 to IEC 60751 | Characteristic curve | Temperature-linear | Type of connection | 2-, 3- or 4-wire circuit | Resolution | 14 bit | Measuring accuracy | | | < 0.25 °C (0.45 °F) | | < 0.1 % of span | Repeatability | < 0.1 °C (0.18 °F) | Measuring current | approx. 0.4 mA | Measuring cycle | < 0.7 s | Measuring range | -200 ... +850 °C (-328 ... +1562 °F) | Measuring span | 25 ... 1050 °C (77 ... 1922 °F) | Unit | °C or °F | Offset | programmable: -100 ... +100 °C (-180 ... +180 °F) | Line resistance | Max. 20 Ω (total from feeder and return conductor) | Noise rejection | 50 and 60 Hz | Output | | Output signal | 4 ... 20 mA, two-wire | Auxiliary power supply | 8.5 ... 36 V DC (30 V for Ex) | Max. load | (Uaux – 8.5 V)/0.023 A | Overrange | 3.6 ... 23 mA, infinitely adjustable (default value: 3.84 ... 20.5 mA) | Error signal (in the event of sensor breakage) | 3.6 ... 23 mA, infinitely adjustable (default value: 3.6 mA or 22.8 mA) | Damping time | 0 ... 30 s | Protection | Against reversed polarity | Resolution | 12 bit | Accuracy at 23 °C (73.4 °F) | < 0.1 % of span | Temperature effect | < 0.1 %/10 °C (0.1 %/18 °F) | Effect of auxiliary power | < 0.01 % of span/V | Effect of load impedance | < 0.025 % of max. span/100 Ω | Long-term drift | | | < 0.025 % of max. span | | < 0.035 % of max. span | | < 0.05 % of max. span | Ambient conditions | | Ambient temperature range | -40 ... +85 °C (-40 ... +185 °F) | Storage temperature range | -40 ... +85 °C (-40 ... +185 °F) | Relative humidity | 98 %, with condensation | Electromagnetic compatibility | According to EN 61326 and NAMUR NE21 | Construction | | Weight | 50 g | Dimensions | See dimensional drawing | Material | Molded plastic | Cross-section of cables | Max. 2.5 mm2 (AWG 13) | Degree of protection to IEC 60529 | | | IP40 | | IP00 | Certificates and approvals | | Explosion protection ATEX | | EC type test certificate | PTB 05 ATEX 2049X | - "Intrinsic safety" type of protection
| II 1G EEx ia IIC T6/T4 II 2(1)G EEx ib/ia IIC T6/T4 | - "Operating equipment that is non-ignitable and has limited energy" type of protection
| II 3G EEx nAL IIC T6/T4 | Explosion protection: FM for USA | | | PID 3024169 | | IS/Cl I, II, III/Div 1/GP ABCDEFG T4, T5, T6 IS/Cl I/ZN 0, 1/AEx ia IIC T4, T5, T6 Nl/Cl I, II, III/Div 2/GP ABCDFG T4, T5, T6 Cl I/ZN 2/GP IIC T4, T5, T6 | Explosion protection to FM for Canada (cFMUS) | | | PID 3024169 | | IS/Cl I, II, III/Div 1/GP ABCDEFG T4, T5, T6 IS/Cl I/ZN 0, 1/AEx ia IIC T4, T5, T6 Nl/Cl I, II, III/Div 2/GP ABCDFG T4, T5, T6 Cl I/ZN 2/GP IIC T4, T5, T6 | | | Software requirements for SIPROM T | | PC operating system | Windows ME, 2000 and XP; also Windows 95, 98 and 98SE, but only in connection with RS 232 modem. | Factory setting: | | - Pt100 (IEC 751) with 3-wire circuit
- Measuring range: 0 ... 100 °C (32 ... 212 °F)
- Error signal in the event of sensor breakage: 22.8 mA
- Sensor offset: 0 °C (0 °F)
Damping 0.0 s |
|
|